3BHS212794 E01 REV M
ACS6000
USER MANUAL
191/278
08 OPERATION
• When alarms and faults are not present and the drive is ready, the
INU CDP control panel displays ReadyOn.
4.
Press the
SUPPLY ON
push button on the door of the control unit to
charge the DC link.
The push button flashes during charging.
The status line of the control panel alternates between Charging
and AuxiliaryOn.
Note:
After charging has been finished, the following takes place:
• Main circuit breaker closes automatically.
• SUPPLY ON push button lights up permanently.
• Drives with an ARU:
- The ARU is now “ReadyRun”.
1 L ->
0.0 rpm
StateINU
ReadyOn
DC VOLT
0.00 rpm
PRI VOLT
0 kW
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP
0.00 rpm
POWER
0.0 kW
Alternating display message:
• Charging
• AuxiliaryOn
1 L -> 0.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
4840.0 V 0
StateARU
ReadyRun
DC Voltage 4400.0 V
COS PHI
0.2