![ABB ACS 6000 User Manual Download Page 187](http://html.mh-extra.com/html/abb/acs-6000/acs-6000_user-manual_2952187.webp)
3BHS212794 E01 REV M
ACS6000
USER MANUAL
187/278
08 OPERATION
8.8.2
Stop sequence of the drive
1) Operation
2) ReadyRef
3) Stop command
4) Stopping
• Speed ramps down
• INU stops modulating
5) Off command
• Stop command to ARU (only in drives with an ARU)
• MCB opens
• DC link discharges
• Cooling system switches off after a delay
6) ReadyRun
7) ARU ReadyOn
• Only in drives with an ARU
8) ReadyOn
• Drive is grounded
• Doors in medium voltage units are released for opening
• Auxiliary power supply switched off
9) NotReadyOn