198 Parameters
Defines the start limit for the sleep function. If
the value is 0.0, set 1 sleep mode is disabled.
The sleep function compares PID output
) to the
value of this parameter. If PID output remains
below this value longer than the sleep delay
defined by
, the drive
enters the sleep mode and stops the motor.
0.0
0.0...200000.00
Sleep start level.
1 = 1
Defines a delay before the sleep function actually
becomes enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is
enabled by parameter
, and
resets when the sleep mode is disabled.
60.0
0.0…3600.0 s
Sleep start delay.
1 = 1
Defines a boost time for the sleep boost step.
See parameter
0.0
0.0...200000.00
Sleep boost time.
1 = 1
When the drive is entering sleep mode, the
process setpoint is increased by this value for
the time defined by parameter
If active, sleep boost is aborted when the drive
wakes up.
0.00
0.00…
32767.00%
Sleep boost step.
1 = 1
Defines the wake-up level as deviation between
process setpoint and feedback.
When the deviation exceeds the value of this
parameter, and remains there for the duration of
the wake-up delay (
), the
drive wakes up.
See also parameter
.
0.00
-200000.00...
200000.00
Wake-up level (as deviation between process
setpoint and feedback).
1 = 1
Defines a wake-up delay for the sleep function to
prevent nuisance wake-ups. See parameter
.
The delay timer starts when the deviation
exceeds the wake-up level (
), and resets if the deviation falls below
the wake-up level.
0.50
0.00…60.00 s
Wake-up delay.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACQ80
Page 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Page 2: ... Related documents are listed on page 13 ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Startup control with I O and ID run ...
Page 34: ...34 Using the control panel ...
Page 74: ...74 Program features ...
Page 78: ...78 Control macros ...
Page 380: ...380 Fieldbus control through a fieldbus adapter ...
Page 384: ...384 Parameterization with Drive Composer ...
Page 388: ...388 Parameterization with Automation builder drive manager ...