R6, R7: 400 mm (15.75”)
in)
R8, R9: 500 mm (19.68 in)
R10. R11: 800 mm (31.50 in)
Maximum allowed plinth height for the extraction/installation
ramp
The maximum plinth height for the extraction/installation ramp delivered with the drive
is 50 mm (1.97 in).
Typical power cable sizes
The table below gives typical copper and aluminum cable types with concentric copper
shield for the drives with nominal current. For the cable sizes accepted by the drive
cabinet cable entries and connection terminals, see
Terminal and entry data for the
US 2)
IEC 1)
Frame size
ACQ580-
07…
Cu cable type
Al cable type
Cu cable type
AWG/kcmil per
phase
mm2
mm2
U
n = 400 V
3/0
3×120
3×95
R6
0145A-4
250 MCM
3×150
3×120
R7
0169A-4
300 MCM
3×240
3×150
R7
0206A-4
2×2/0
2×(3×95)
2×(3×70)
R8
0246A-4
2×3/0
2×(3×120)
2×(3×95)
R8
0293A-4
2×250 MCM
2×(3×185)
2×(3×120)
R9
0363A-4
2×300 MCM
2×(3×240)
2×(3×150)
R9
0430A-4
2×500 MCM or 3×250
MCM
3×(3×150)
3×(3×95)
R10
0505A-4
3×300 MCM
4×(3×150)
3×(3×120)
R10
0585A-4
3×300 MCM
4×(3x×150)
3×(3×150)
R10
0650A-4
3×500 MCM or 4×300
MCM
4×(3×185)
3×(3×185)
R11
0725A-4
3×600 MCM or 4×400
MCM
4×(3×240)
3×(3×240)
R11
0820A-4
Technical data 207
Summary of Contents for ACQ580-07
Page 1: ... ABB DRIVES FOR WATER ACQ580 07 Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...4 Update notice ...
Page 20: ...16 ...
Page 26: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 22 Safety instructions ...
Page 32: ...28 ...
Page 38: ...34 ...
Page 66: ...62 ...
Page 69: ...Mechanical installation 65 ...
Page 73: ... Mechanical installation 69 ...
Page 75: ...Declaration of Conformity Mechanical installation 71 ...
Page 108: ...104 ...
Page 133: ...Electrical installation 129 ...
Page 142: ...138 ...
Page 156: ...152 ...
Page 162: ...158 ...
Page 171: ...Maintenance 167 ...
Page 177: ...3 4 Maintenance 173 ...
Page 184: ...14 13 15 16 17 Remove the flange 180 Maintenance ...
Page 187: ...3 4 5 6 Remove the mounting plate Maintenance 183 ...
Page 189: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 185 ...
Page 193: ...4 5 3 6 Remove the mounting plate Maintenance 189 ...
Page 195: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 191 ...
Page 218: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 214 Technical data ...
Page 233: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 229 ...
Page 257: ...13 Dimension drawings Example dimension drawings are shown below Dimension drawings 253 ...
Page 258: ...Frames R6 and R7 IP21 UL Type 1 254 Dimension drawings ...
Page 259: ...Frames R6 and R7 B054 IP42 UL Type 1 Filtered Dimension drawings 255 ...
Page 260: ...Frames R6 and R7 B055 IP54 UL Type 12 256 Dimension drawings ...
Page 261: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 257 ...
Page 262: ...Frames R6 and R7 F289 258 Dimension drawings ...
Page 263: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 259 ...
Page 264: ...Frames R8 and R9 IP21 UL Type 1 260 Dimension drawings ...
Page 265: ...Frames R8 and R9 B054 IP42 UL Type 1 Filtered Dimension drawings 261 ...
Page 266: ...Frames R8 and R9 B055 IP54 UL Type 12 262 Dimension drawings ...
Page 267: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 263 ...
Page 268: ...Frames R8 and R9 F289 264 Dimension drawings ...
Page 269: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 265 ...
Page 295: ... Declaration of conformity The Safe torque off function 291 ...
Page 296: ...292 ...
Page 302: ...298 ...
Page 309: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 305 ...
Page 310: ...306 ...
Page 316: ...312 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...
Page 322: ...318 ...