ACQ550-U1 User’s Manual
161
Group 64: LOAD ANALYZER
This group defines the load analyzer, which can be used for analyzing the
customer’s process and sizing the drive and the motor.
The peak value is logged at 2 ms level, and the distribution loggers are updated on
0.2 s (200 ms) time level. Three different values can be logged.
1. Amplitude logger 1: The measured current is logged continuously. The
distribution as a percentage of the nominal current
I
2N
is shown in ten classes.
2. Peak value logger: One signal in group 1 can be logged for the peak (maximum)
value. The peak value of the signal, peak time (time when the peak value was
detected) as well the frequency, current and DC voltage at the peak time are shown.
3. Amplitude logger 2: One signal in group 1 can be logged for amplitude
distribution. The base value (100% value) can be set by the user.
The first logger cannot be reset. The other two loggers can be reset by a user-
defined method. They are also reset if either of the signals or the peak value filter
time is changed.
Code Description
6401
PVL SIGNAL
Defines (by number) the signal logged for the peak value.
• Any parameter number in
can be selected. Eg 102 = parameter 0102
SPEED
.
100 =
NOT
SELECTED
– No signal (parameter) logged for the peak value.
101…178 – Logs parameter 0101…0178.
6402
PVL FILTER TIME
Defines the filter time for peak value logging.
• 0.0…120.0 – Filter time (seconds).
6403
LOGGERS RESET
Defines the source for the reset of peak value logger and amplitude logger 2.
0 =
NOT
SEL
– No reset selected.
1 =
DI
1 – Reset loggers on the rising edge of digital input
DI
1.
2…6 =
DI
2…
DI
6 – Reset loggers on the rising edge of digital input
DI
2…
DI
6.
7 =
RESET
– Reset loggers. Parameter is set to
NOT
SEL
.
-1 =
DI
1(
INV
) – Reset loggers on the falling edge of digital input
DI
1.
-2…-6 =
DI
2(
INV
) …
DI
6(
INV
) – Reset loggers on the falling edge of digital input
DI
2…
DI
6.
6404
AL2 SIGNAL
Defines the signal logged for amplitude logger 2.
• Any parameter number in
can be selected. Eg 102 = parameter 0102
SPEED
.
100 =
NOT
SELECTED
– No signal (parameter) logged for amplitude distribution (amplitude logger 2).
101…178 – Logs parameter 0101…0178.
6405
AL2 SIGNAL BASE
Defines the base value from which the percentage distribution is calculated.
• Representation and default value depends on the signal selected with parameter 6404
AL
2
SIGNAL
.
6406
PEAK VALUE
Detected peak value of the signal selected with parameter 6401
PVL
SIGNAL
.
6407
PEAK TIME 1
Date of the peak value detection.
• Format: Date if the real time clock is operating (dd.mm.yy). / The number of days elapsed after the power-on if the
real time clock is not used, or was not set (xx d).
6408
PEAK TIME 2
Time of the peak value detection.
• Format: hours:minutes:seconds.
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...