
140
ACQ550-U1 User’s Manual
3612
START DAY 3
Defines timer 3 weekly start day.
• See parameter 3604.
3613
STOP DAY 3
Defines timer 3 weekly stop day.
• See parameter 3605.
3614
START TIME 4
Defines timer 4 daily start time.
• See parameter 3602.
3615
STOP TIME 4
Defines timer 4 daily stop time.
• See parameter 3603.
3616
START DAY 4
Defines timer 4 weekly start day.
• See parameter 3604.
3617
STOP DAY 4
Defines timer 4 weekly stop day.
• See parameter 3605.
3622
BOOSTER SEL
Selects the source for the booster signal.
0 =
NOT
SEL
– Booster signal is disabled.
1 =
DI
1 – Defines
DI
1 as the booster signal.
2…6 =
DI
2…
DI
6 – Defines
DI
2…
DI
6 as the booster signal.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the booster signal.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the booster signal.
3623
BOOSTER TIME
Defines the booster ON time. Time is started when booster sel
signal is released. If parameter value is 01:30:00, booster is
active for 1 hour and 30 minutes after activation DI is released.
3626
TIMED FUNC 1 SRC
Defines the time periods used by the timer.
0 =
NOT
SEL
– No time periods have been selected.
1 =
T
1 – Time Period 1 selected in the timer.
2 =
T
2 – Time Period 2 selected in the timer.
3 =
T
1+
T
2 – Time Periods 1 and 2 selected in the timer.
4 =
T
3 – Time Period 3 selected in the timer.
5 =
T
1+
T
3 – Time Periods 1 and 3 selected in the timer.
6 =
T
2+
T
3 – Time Periods 2 and 3 selected in the timer.
7 =
T
1+
T
2+
T
3 – Time Periods 1, 2 and 3 selected in the timer.
8 =
T
4 – Time Period 4 selected in the timer.
9 =
T
1+
T
4 – Time Periods 1 and 4 selected in the timer.
10 =
T
2+
T
4 – Time Periods 2 and 4 selected in the timer.
11 =
T
1+
T
2+
T
4 – Time Periods 1, 2 and 4 selected in the timer.
12 =
T
3+
T
4 – Time Periods 3 and 4 selected in the timer.
13 =
T
1+
T
3+
T
4 – Time Periods 1, 3 and 4 selected in the timer.
14 =
T
2+
T
3+
T
4 – Time Periods 2, 3 and 4 selected in the timer.
15 =
T
1+
T
2+
T
3+
T
4 – Time Periods 1, 2, 3 and 4 selected in the timer.
16 =
BOOSTER
– Booster selected in the timer.
17 =
T
1+
B
– Booster and Time Period 1 selected in the timer.
18 =
T
2+
B
– Booster and Time Period 2 selected in the timer.
19 =
T
1+
T
2+
B
– Booster and Time Periods 1 and 2 selected in the timer.
20 =
T
3+
B
– Booster and Time Period 3 selected in the timer.
Code Description
Booster active
Activation DI
Booster time
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...