Embedded fieldbus
Troubleshooting
The troubleshooting table below should be followed in order from top to bottom by
parameter number. Begin the troubleshooting process by displaying the first
parameter in the table (5308) and determining if the display on the panel exhibits the
symptom. If it does, review the possible cause(s) and take the necessary corrective
action(s). Once the symptom for this parameter is eliminated, continue to the next
parameter and repeat the process until you have reached the end.
Parameter
Number
Display on
Panel
(Symptom)
Possible Cause
Corrective Action
5308
UART
ERRORS
Rapidly
Increasing
Numeric
Value
1
1. Duplicate
Addresses
2. Swapped Wires
3. Incorrect Baud Rate
4. Incorrect Parity
5. Too many devices
on wire
6. Incorrect Bias
7. Noise on EIA-485
wire
8. Blown EIA-485
transceiver
1. Ensure EFB PROTOCOL parameters
5302 [also 5311 & 5317 when using
BACnet] are unique. 5302 must be a
unique address on the segment. [5311 &
5317 must be unique addresses on the
network when using BACnet.]
2. Swap wires B(+) & A(-).
3. Adjust parameter 5303 & Cycle power.
4. Change parity using parameter 5304 &
cycle power.
5. Limit to 31 devices on 1 segment.
6. Turn off VFD termination resistors (move
jumpers). Install loose resistor
recommended by the DCS controls
company. (Terminate final device on the
trunk.)
7. Install EIA-485 (3 conductor shielded)
data grade cable communications wire.
See drawings on page
8. Find and correct ground loop or high
voltage problems before replacing any
component assemblies.
Perform the following steps to determine if
the EIA-485 transceiver is damaged.
a. Power unit down.
b. Remove bus wires and retighten
connections.
c. Turn bus termination ON.
d. Measure impedance between B(+) &
A(-).
ACQ550 164 ohms +/- 5%
If measurements are not within the
specified range the EIA-485 transceiver is
bad, replace the assembly containing the
EIA-485 port.
5307
(5007)
DV CRC
ERR
Rapidly
Increasing
Numeric
Value
1
1. Duplicate
Addresses
2. Too many devices
on wire
3. Noise on EIA-485
wire
1. See Corrective Action 1. Parameter
Number 5308
2. Limit to 31 unit loads on 1 segment
(ACQ550 = 1 unit load)
3. See Corrective Action 7. Parameter
Number 5308
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...