Group 01: OPERATING DATA
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Code Description
0101
SPEED & DIR
The calculated signed speed of the motor (rpm). The absolute value of 0101
SPEED
&
DIR
is the same as the value of
0102
SPEED
.
• The value of 0101
SPEED
&
DIR
is positive if the motor runs in the forward direction.
• The value of 0101
SPEED
&
DIR
is negative if the motor runs in the reverse direction.
0102
SPEED
The calculated speed of the motor (rpm). (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0103
OUTPUT FREQ
The frequency (Hz) applied to the motor. (Parameter 0102 or 0103 is shown by default in the control panel Output
mode.)
0104
CURRENT
The motor current, as measured by the ACQ550. (Shown by default in the control panel Output mode.)
0105
TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque. (Shown by default in the
control panel Output mode.)
0106
POWER
The measured motor power in kW.
0107
DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the ACQ550.
0109
OUTPUT VOLTAGE
The voltage applied to the motor.
0110
DRIVE TEMP
The temperature of the drive power transistors in degrees Celsius.
0111
EXTERNAL REF 1
External reference,
REF
1, in rpm or Hz – units determined by parameter 9904.
0112
EXTERNAL REF 2
External reference,
REF
2, in %.
0113
CTRL LOCATION
Active control location. Alternatives are:
0 =
LOCAL
1 =
EXT
1
2 =
EXT
2
0114
RUN TIME (R)
The drive’s accumulated running time in hours (h).
• Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115
KWH COUNTER (R)
The drive’s accumulated power consumption in kilowatt hours.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be
reset
by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0116
APPL BLK OUTPUT
Application block output signal. Value is from either:
• PFC control, if PFC Control is active, or
• Parameter 0112
EXTERNAL
REF
2.
Summary of Contents for ACQ550-x1-06A6-2
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...