ACH580 E-Clipse bypass and packaged drive user manual
17
Installation
Install the control wiring
Connect control wiring to terminal block X1 on the ACH580 control board and to
terminal block X2 on the E-Clipse Bypass control board. For more information on
these connections, refer to the following:
• X1 terminal block location and terminal data are defined in the
Installation
instructions for the drive on page
5
.
• X2 terminal block location is illustrated in the figures starting with
wiring diagrams – Vertical E-Clipse Bypass
on page
• X2 terminal data are provided in
Basic control connections for E-Clipse HVAC
on page
• Basic connections are described in the following paragraphs. Alternate
configurations using the E-Clipse Bypass macro are described in the
ACH580
HVAC control program firmware manual
(3AXD50000027537).
• On Terminal Block X1 inside the ACH580, analog inputs and outputs and
additional digital input and relay output connections (AI1, AI2, AO1, AO2,
DI1…DI6 and RO1…RO6) are available for use.
Note:
The E-Clipse Bypass control circuitry uses serial communications connections
(X1:29…X1:31) inside the ACH580. These connections are not available for any
other purpose and must not be reconfigured.
Basic connections
The figure on page
shows the basic
control connections for use with the
E-Clipse Bypass HVAC Default macro.
These connections are described in the
following paragraphs.
In typical installations, only analog input
wires connect to the ACH580 terminal
block, with other control connections
made on the E-Clipse Bypass control
board.
Use wire ties to permanently affix control/
communications wiring to the hooked wire
race tie points provided, maintaining a
minimum 6 mm (1/4 in.) spacing from
power wiring.
Drive’s power connection terminals
Refer to the tables in the
section from pages
–
, which list
the maximum power and motor cable
terminal sizes for connections to an input
circuit breaker or disconnect switch, a
motor terminal block and ground lugs. The
tables also list torque that should be
applied when tightening the terminals.
BYPASS CONTROL
ENTER
ESC
ENABLED
SELECTED
FAULTED
HAND
OFF/RESET
AUTO
MOTOR RUN
DRIVE
BYPASS
EIA-485
port
control
terminals
Digital I/O
control
terminals
Bottom view
J7
connection
J8
connection
GND J6
J2
connection
Summary of Contents for ACH580 Series
Page 2: ......
Page 11: ...ACH580 BCR BDR VCR VDR E Clipse Bypass Drives 1 200 HP ...
Page 35: ...26 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 43: ...34 ACH580 E Clipse bypass and packaged drive user manual Start up ...
Page 67: ...58 ACH580 E Clipse bypass and packaged drive user manual Application macros ...
Page 193: ...184 ACH580 E Clipse bypass and packaged drive user manual Fieldbus adapter ...
Page 207: ...198 ACH580 E Clipse bypass and packaged drive user manual Diagnostics ...
Page 229: ...220 ACH580 E Clipse bypass and packaged drive user manual Technical data ...
Page 231: ...ACH580 PCR PDR Packaged Drives with Disconnect 1 200 HP ...
Page 243: ...234 ACH580 E Clipse bypass and packaged drive user manual Installation ...
Page 256: ......