Make sure that the drive is compatible with the grounding
system
The standard drive with internal EMC E210 and the ground-to-phase varistor
connected can be installed to a symmetrically grounded TN-S system. If you install
the drive to another system, you may need to disconnect the EMC filter and
ground-to-phase varistor.
Do not install the drive with the EMC filter and the ground-to-phase varistor
connected to a system that they are not suitable for. If you do, it can cause
danger or damage the drive.
Do not install the drive on a corner-grounded or midpoint-grounded delta
system. Disconnecting the EMC filter and ground-to-phase varistor does not
prevent damage to the drive.
TT systems
1) 2)
IT systems (ungrounded or high-
resistance grounded)
Symmetrically grounded TN-S
systems (centergrounded wye)
Disconnect VAR wire.
Disconnect EMC AC and VAR
wires.
Do not disconnect EMC AC and
VAR wires.
1) A residual current device must be installed in the supply system. In NEC installations the residual current device is
only required at or above 1000 amps.
2) ABB does not guarantee the EMC category or the operation of the ground leakage detector built inside the drive.
■
Disconnecting instructions
EMC AC and varistor (VAR) grounding wires are located at the top of the circuit board
compartment. Disconnect them (1) and attach them with the nearby plastic clamp (2).
1
2
Move the drive to the installation site and unpack it
Move the transport package by pallet truck to the installation site.
To unpack the package:
•
Cut the straps.
•
Lift the lid.
EN – Quick installation and start-up guide 7
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
SV
TR
ZH
Summary of Contents for ACH580-34
Page 2: ......
Page 44: ...44 ...
Page 176: ...176 ...
Page 242: ...242 ...
Page 264: ...264 ...
Page 284: ...284 ...
Page 306: ...306 Step by step drawings for an installation example in Rittal VX25 800 mm wide enclosure ...