![ABB ACH580-34 Quick Installation And Start-Up Manual Download Page 285](http://html.mh-extra.com/html/abb/ach580-34/ach580-34_quick-installation-and-start-up-manual_3045231285.webp)
Technical data and references
IEC ratings
Output ratings
Max. cur-
rent
Input rat-
ing
1)
Frame
ACH580-
34-…
Heavy-duty
use
Light-duty use
Nominal use
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
kW
A
kW
A
kW
A
A
A
3-phase
U
n
= 400 V
110
206
132
234
132
246
350
212
R11
246A-4
132
246
160
278
160
293
418
257
R11
293A-4
160
293
200
347
200
365
498
321
R11
365A-4
200
365
250
420
250
442
621
401
R11
442A-4
200
365
250
480
250
505
631
401
R11
505A-4
250
442
315
556
315
585
751
505
R11
585A-4
250
505
355
618
355
650
859
569
R11
650A-4
3-phase
U
n
= 480 V
150
180
200
240
200
240
350
209
R11
246A-4
200
240
200
260
200
260
418
233
R11
293A-4
250
302
300
361
300
361
498
307
R11
365A-4
300
361
350
414
350
414
621
363
R11
442A-4
300
361
350
414
350
414
631
363
R11
505A-4
350
414
350
430
350
430
751
389
R11
585A-4
350
430
400
483
400
483
859
441
R11
650A-4
UL (NEC) ratings
Output ratings
Max. cur-
rent
Input rat-
ing
1)
Frame
ACH580-
34-…
Heavy-duty
use
Light-duty use
Nominal use
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
kW
A
kW
A
kW
A
A
A
3-phase
U
n
= 480 V
150
180
200
240
200
240
350
209
R11
240A-4
200
240
250
302
250
302
498
258
R11
302A-4
250
302
300
361
300
361
542
307
R11
361A-4
300
361
350
414
350
414
614
363
R11
414A-4
350
414
400
477
400
477
704
418
R11
477A-4
Technical data and references 285
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
SV
TR
ZH
Summary of Contents for ACH580-34
Page 2: ......
Page 44: ...44 ...
Page 176: ...176 ...
Page 242: ...242 ...
Page 264: ...264 ...
Page 284: ...284 ...
Page 306: ...306 Step by step drawings for an installation example in Rittal VX25 800 mm wide enclosure ...