ACH550-UH User’s Manual
1-263
Fieldbus adapter
•
The serial communication channel is defined as the source for controlling
commands from EXT1 (set using parameters 1001 EXT1 COMMANDS and 1102
EXT1/EXT2 SEL).
•
The external plug-in fieldbus adapter is activated:
– Parameter 9802 COMM PROT SEL = 4 (EXT FBA).
– The external plug-in fieldbus adapter is configured to use the drive profile
mode or drive profile objects.
The content of the
CONTROL
WORD
depends on the protocol/profile used. See the
user’s manual provided with the FBA module and/or the
Status Word
The
STATUS
WORD
is a 16-bit word containing status information, sent by the drive to
the fieldbus controller. The content of the
STATUS
WORD
depends on the protocol/
profile used. See the user’s manual provided with the FBA module and/or the
section.
Reference
The contents of each
REFERENCE
word:
•
Can be used, as speed or frequency reference.
•
Is a 16-bit word comprised of a sign bit and a 15-bit integer.
•
Negative references (indicating reversed rotation direction) are indicated by the
two’s complement of the corresponding positive reference value.
The use of a second reference (REF2) is supported only when a protocol is
configured for the ABB Drives profile.
Reference scaling is fieldbus type specific. See the user’s manual provided with the
FBA module and/or the following sections as appropriate:
•
ABB drives profile technical data
•
Generic profile technical data
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example, group 01 parameters) can be mapped to
Input Words using group 51 parameters (protocol-dependent, but typically
parameters 5104…5126).
Planning
Network planning should address the following questions:
•
What types and quantities of devices must be connected to the network?
•
What control information must be sent down to the drives?
•
What feedback information must be sent from the drives to the controlling
system?
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...