Group 23: SPEED CONTROL
This group defines variables used for speed control operation.
Group 23: Speed Control
Code Description Range
Resolution
Default
S
2301
PROP GAIN
0.00…200.00
0.01
3.00
Sets the relative gain for the speed controller.
• Larger values may cause speed oscillation.
• The figure shows the speed controller output
after an error step (error remains constant).
Note:
You can use parameter 2305
AUTOTUNE
RUN
to automatically set the proportional
gain.
2302
INTEGRATION TIME
0.00…600.00 s
0.01 s
0.50 s
Sets the integration time for the speed
controller.
• The integration time defines the rate at which
the controller output changes for a constant
error value.
• Shorter integration times correct continuous
errors faster.
• Control becomes unstable if the integration
time is too short.
• The figure shows the speed controller output
after an error step (error remains constant).
Note:
You can use parameter 2305
AUTOTUNE
RUN
to automatically set the integration time.
2303
DERIVATION TIME
0…10000 ms
1 ms
0 ms
Sets the derivation time for the speed controller.
• Derivative action makes the control more responsive to error value changes.
• The longer the derivation time, the more the speed controller output is boosted during the change.
• If the derivation time is set to zero, the controller works as a PI controller, otherwise as a PID controller.
The figure below shows the speed controller output after an error step when the error remains constant.
Gain = K
p
= 1
T
I
= Integration time = 0
T
D
= Derivation time = 0
Error value
Controller output
%
e = Error value
t
Controller
output =
K
p
· e
T
I
Controller output
%
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time = 0
K
p
· e
e = Error value
K
p
· e
t
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time > 0
T
s
= Sample time period = 2 ms
Δ
e = Error value change between two samples
T
I
K
p
· e
Error value
Controller output
%
e = Error value
K
p
·
T
D
·
Δ
e
T
s
K
p
· e
t
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...