1-132
ACH550-UH User’s Manual
Parameters
3023
WIRING FAULT
0, 1
1
1 (
ENABLE
)
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
• Improper connections of input power to the drive output (the drive can display fault 35,
OUTPUT
WIRING
if improper
connections are detected).
• Ground faults (the drive can display fault 16,
EARTH
FAULT
if a ground fault is detected). Also, see parameter 3017
EARTH
FAULT
.
0 =
DISABLE
– No drive response to either of the above monitoring results.
Note:
Disabling wiring fault (ground fault) may void the warranty.
1 =
ENABLE
– The drive displays faults when this monitoring detects problems.
3024
CB TEMP FAULT
0, 1
1
1 (
ENABLE
)
Defines the drive response to control board overheating. Not for drives with an OMIO control board.
0 =
DISABLE
– No response.
1 =
ENABLE
– Displays fault 37 (
CB
OVERTEMP
) and the drive coasts to stop.
Group 30: Fault Functions
Code Description Range
Resolution
Default