Alarm and Event Handling
Section 6 Program Code Issues
98
3BSE042835-600
summarizes the Alarm and Event parameters for the Standard Library
Objects and
illustrates the alarm and event logic.
Table 13. Summary of Alarm and Event parameters
Parameter
Direction Data type
Function
AEClass
In
Dint
The class for all alarms in the
object.
AEConfigX
In
Dint
Defines whether condition X
should generate an alarm or event.
Possible values are 0-4 (see
above). This parameter should be
used as a configuration parameter.
AESeverityX
In
Dint
Severity for alarm condition X.
CondNameX
In
String[15] Name of the condition X. Shall
have a NLS-treated default value.
EnableX
In
Bool
If false, the XStat (and XAct)
output is kept false and the
alarm/event generation is disabled.
InteractionPar.EnableX In
Bool
Same as EnableX but controlled
from faceplate. This component is
harmonized with EnableX and
actions from the alarm list. For
example, if condition X is disabled
from the alarm list,
InteractionPar.EnableX is set to
false.
When declaring the data type for
InteractionPar, the EnableX
component must be declared with
the attribute “retain”.
InhXAct
In
Bool
Inhibits the XAct output. Only
introduced for a selection of
objects.
Summary of Contents for AC 800M
Page 2: ......
Page 3: ...AC 800M Library Object Style Guide System Version 6 0...
Page 12: ...Related Documentation About This User Manual 12 3BSE042835 600...
Page 18: ...Naming Convention Section 1 Libraries 18 3BSE042835 600...
Page 108: ...SIL Mark Restrictions Section 6 Program Code Issues 108 3BSE042835 600...
Page 116: ...Standard Library Parameters Appendix A Names and Abbreviations 116 3BSE042835 600...
Page 119: ......