14. Technical data
Table 1. Dimensions
Description
Value
Width
440 mm / 17.3”
Height
88 mm / 3.4”
Depth
220 mm / 8.6”
Weight
6.0kg
Mounting
2U Rack mount (19”), fits into standard 19” rack
Table 2. Power supply
Description
High Voltage variant
Low Voltage variant
Nominal auxiliary voltage Un
100...240 VAC 50 and 60Hz
36...72 VDC
100...240 VDC
Maximum interruption time in the auxiliary DC voltage
without resetting the device
50 ms at Un
Auxiliary voltage variation
85...110% of Un (85...264VAC)
80...117% of Un (80...280
VDC)
Start-up threshold
Power consumption
35 W (Typical)
35 W (Typical)
Ripple in the DC auxiliary voltage
Max 10% of the DC value (at frequency of 100 Hz)
Fuse type
Table 3. Front port Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP protocol
Standard Ethernet CAT 5 cable with RJ-
45 connector
100 MBits/s
Table 4. Environmental conditions
Description
Value
Operating temperature range
-20...+55ºC (continuous)
Short-time
Short-time service temperature range
-25...+70ºC (<16h)
1, 2
Relative humidity
<95%, non-condensing
Atmospheric pressure
Altitude
Transport and storage temperature range
-30...+85ºC
Table 5. Electromagnetic Compability (EMC)
Description
IEC 61850-3 Reference
Requirement
Test standard
Test ports
Electrostatic discharge
6.7.3
6 kV contact
8 kV air
IEC 6100-4-2
E
Radiated, radiofrequency
electromagnetic field 80
MHz - 3000 MHz
6.7.3
AM 80% 1kHz, 10 V/m
IEC 6100-4-3
E
Fast transient/burst
6.7.3
4 KV
IEC 6100-4-4
A,B,D
Surge
6.7.3
line to ground 4,0 kV
line to line 2,0 kV
IEC 6100-4-5
A,B
Induced by radio frequency fields
6.7.3
AM 80% 1kHz, 10 V
IEC 6100-4-6
A,B,D
Power frequency magnetic field
6.7.3
100 A/m continuous
1000 A/m 1s
IEC 6100-4-8
E
Voltage dips
Voltage interruptions
6.7.3
ΔU 30% for 1 period
ΔU 60% for 50 period
ΔU 100% for 5 period
ΔU 100% for 50 period
IEC 6100-4-11
A
1 Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC