15. Protection functions
Table 12. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
PHLPTOC
Depending on the frequency of the measured current: fn
±2 Hz
±1.5% of the set value or ±0.002 × In
PHHPTOC and
PHIPTOC
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1…10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Start time
3, 4
PHIPTOC:
IFault = 2 × set
Start value
IFault = 10 × set
Start value
Minimum
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
PHHPTOC and
PHLPTOC:
IFault = 2 × set
Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
5
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
Table 13. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
PHLPTOC
0.05...5.00 × In
0.01
PHHPTOC
0.10...40.00 × In
0.01
PHIPTOC
1.00...40.00 × In
0.01
Time multiplier
PHLPTOC and
PHHPTOC
0.05...15.00
0.01
Operate delay time
PHLPTOC and
PHHPTOC
40...200000 ms
10
PHIPTOC
40...200000 ms
10
Operating curve type
6
PHLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
PHHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
PHIPTOC
Definite time
Table 14. Three-phase directional overcurrent protection (DPHxPDOC)
Characteristic
Value
Operation accuracy
EFLPTOC
Depending on the frequency of the measured current: fn
±2 Hz
±1.5% of the set value or ±0.002 × In
EFHPTOC and
EFIPTOC
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1…10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Start time
7, 8
EFIPTOC:
IFault = 2 × set Start value
IFault = 10 × set Start value
Minimum
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and EFLPTOC:
IFault = 2 × set Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
3 Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
4 Includes the delay of the signal output contact
5 Includes the delay of the heavy-duty output contact
6 For further reference, see the Operation characteristics table
7 Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
8 Includes the delay of the signal output contact