Product version: 1.0
Table 43. Three-phase underimpedance protection (UZPDIS)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current and voltage: fn ±2 Hz
±3.0% of the set value or ±0.2 %Zb
Start time
42, 43
Typically 50 ms
Reset time
Typically 40 ms
Reset ratio
Typically 1.04
Retardation time
<40 ms
Operate time accuracy
±1.0% of the set value or ±20 ms
Table 44. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
Current measurement: ±1.5% of the set value or ±0.002 × In (at currents in the
range of 0.01...4.00 × In)
Operate time accuracy
44
±2.0% of the theoretical value or ±0.50 s
Table 45. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR) main settings
Parameter
Function
Value (Range)
Step
Env temperature Set
T1PTTR
-50...100°C
1
Current reference
T1PTTR
0.05...4.00 × In
0.01
Temperature rise
T1PTTR
0.0...200.0°C
0.1
Time constant
T1PTTR
60...60000 s
1
Maximum temperature
T1PTTR
20.0...200.0°C
0.1
Alarm value
T1PTTR
20.0...150.0°C
0.1
Reclose temperature
T1PTTR
20.0...150.0°C
0.1
Current multiplier
T1PTTR
1...5
1
Initial temperature
T1PTTR
-50.0...100.0°C
0.1
Table 46. Circuit breaker failure protection (CCBRBRF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Operate time accuracy
±1.0% of the set value or ±20 ms
Reset time
Typically 40 ms
Retardation time
<20 ms
Table 47. Circuit breaker failure protection (CCBRBRF) main settings
Parameter
Function
Value (Range)
Step
Current value
CCBRBRF
0.05...2.00 × In
0.05
Current value Res
CCBRBRF
0.05...2.00 × In
0.05
CB failure mode
CCBRBRF
1 = Current
2 = Breaker status
3 = Both
-
CB fail trip mode
CCBRBRF
1 = Off
2 = Without check
3 = Current check
-
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
42 fn = 50 Hz, results based on statistical distribution of 1000 measurements
43 Includes the delay of the signal output contact
44 Overload current > 1.2 × Operate level temperature