TITLETEXTFRAME
Product Guide
1MRS758725
SSC600
Product version: 1.0
12
ABB
Characteristic
Value
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±1.0% of the set value or ±20 ms
9
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
Table 15. Three-phase directional overcurrent protection (DPHxPDOC) main settings
Parameter
Function
Value (Range)
Step
Start value
DPHLPDOC
0.05...5.00 × In
0.01
DPHHPDOC
0.10...40.00 × In
0.01
Time multiplier
DPHxPDOC
0.05...15.00
0.01
Operate delay time
DPHxPDOC
40...200000 ms
10
Directional mode
DPHxPDOC
1 = Non-directional
-
2 = Forward
3 = Reverse
Characteristic angle
DPHxPDOC
-179...180°
1
Operating curve type
10
DPHLPDOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
DPHHPDOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Table 16. Non-directional earth-fault protection (EFxPTOC)
Characteristic
Value
Operation accuracy
EFLPTOC
Depending on the frequency of the measured current: fn
±2 Hz
±1.5% of the set value or ±0.002 × In
EFHPTOC and
EFIPTOC
±1.5% of set value or ±0.002 × In (at currents in the range of 0.1…10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Start time
11, 12
EFIPTOC:
IFault = 2 × set Start value
IFault = 10 × set Start value
Minimum
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and EFLPTOC:
IFault = 2 × set Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±1.0% of the set value or ±20 ms
13
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
Table 17. Non-directional earth-fault protection (EFxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 × In
0.005
EFHPTOC
0.10...40.00 × In
0.01
EFIPTOC
1.00...40.00 × In
0.01
Time multiplier
EFLPTOC and EFHPTOC
0.05...15.00
0.01
Operate delay time
EFLPTOC and EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
9 Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
10 For further reference, see the Operating characteristics table
11 Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
12 Includes the delay of the signal output contact
13 Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20