Upload Configuration
Section 3 Configuration
62
3BSE037076-510 D
2.
Select
System Setting
aspect from
Admin Structure
>
Subscriber2, Domain
(System Name).
In this aspect, select
True
in the
Values
column for
Point of Control
(see
).
Figure 38. Enabling the Point of Control through System Setting Aspect
The Point of Control feature is configured by a System Engineer.
Configure permission is required to configure the
Section Definition
aspects.
Add the System Engineer to the Application Engineer group or explicitly provide
the Configure permission to the System Engineer.
Upload Configuration
Ensure that when configuring the
Upload
, the complete section is uploaded. It is not
possible to upload a subsection or a single object that belongs to a complete section.
During upload, the used responsibility configurations are uploaded to the subscriber
system. For more information refer to
Summary of Contents for Ability 800xA Series
Page 2: ......
Page 3: ...System 800xA Multisystem Integration System Version 5 1...
Page 18: ...Prerequisites and Requirements Section 1 Introduction 18 3BSE037076 510 D...
Page 26: ...Medium Large Configuration Section 2 Installation 26 3BSE037076 510 D...
Page 74: ...Limitations Section 3 Configuration 74 3BSE037076 510 D...
Page 98: ...Upgrade Procedure Section 5 Maintenance 98 3BSE037076 510 D...
Page 106: ...Appendix A Error Messages 106 3BSE037076 510 D...
Page 112: ...No System Alarm in the Provider System Appendix B Fault Tracing 112 3BSE037076 510 D...
Page 116: ...Index 116 3BSE037076 510 D Index 116 3BSE037076 510 D...
Page 120: ...Updates in Revision Index D 120 3BSE037076 510 D...
Page 121: ......