Appendix A Error Messages
100
3BSE037076-510 D
Table 8. 800xA Multisystem Integration Error Messages
Error Messages
Description
ABORTED
An upload was aborted by the user.
ACCOUNT_PROMPT_FAILED
*
Internal error. Failed to activate the dialog to input the
connect account. Try to repair the windows installation.
AE_REFERENCE_NOT_FOUND
*
A referenced aspect in the alarm and event system is not
found in the provider.
ASPDIR_DOWN
*
The aspect directory is down on the provider side. Check
the status of the provider.
ASPECT_NOT_FOUND
Internal error. No subscribe information was found for the
proxy aspect. Try to upload all proxy objects again to
regain internal table consistency.
BAD_ID
Internal error. Bad identifier (used in multiple places).
BAD_PASSWORD
The passwords defined for the Remote Access Server
and Client pair do not match each other. Define the
password again both on the provider and subscriber side.
BAD_UNIT_ID
Internal error. Remote Access Server/Client unit did not
exist.
BAD_VERSION
The version of the Remote Access Server and Client is
different and no common version can be found.
Installation of the same version of 800xA Multisystem
Integration on both the provider and subscriber solves the
problem.
CONSYS_INVALIDACCOUNT
*
The account name or password is wrong for the connect
account. The account name must exists as a local user in
the node, or as a domain user.
FILE_ERROR
File error when reading or writing data related to the
Remote Access Client service. Check access to disc and
if the disc is full.
Summary of Contents for Ability 800xA Series
Page 2: ......
Page 3: ...System 800xA Multisystem Integration System Version 5 1...
Page 18: ...Prerequisites and Requirements Section 1 Introduction 18 3BSE037076 510 D...
Page 26: ...Medium Large Configuration Section 2 Installation 26 3BSE037076 510 D...
Page 74: ...Limitations Section 3 Configuration 74 3BSE037076 510 D...
Page 98: ...Upgrade Procedure Section 5 Maintenance 98 3BSE037076 510 D...
Page 106: ...Appendix A Error Messages 106 3BSE037076 510 D...
Page 112: ...No System Alarm in the Provider System Appendix B Fault Tracing 112 3BSE037076 510 D...
Page 116: ...Index 116 3BSE037076 510 D Index 116 3BSE037076 510 D...
Page 120: ...Updates in Revision Index D 120 3BSE037076 510 D...
Page 121: ......