load voltage) / Full
-
load voltage.
12
Heat Release
-
per inverter, full load, typical. Special room cooling may be required.
Specifications
Table 9 Specifications
-
Inverter
SI5A120PME series
SI10A120PME series
SI5A240PME series
+24 Vdc Input
−48
Vdc Input
−48
Vdc Input
Input (per module)
Typical
+21.0 to +32.0 Vdc
24.5 Vdc minimum
+27.0 Vdc
-
42.5 to
−60.0
Vdc
49.6 Vdc minimum
−54.0
Vdc
-
42.5 to
−60.0
Vdc
−49.6
Vdc minimum
−54.0
Vdc
35.0 A maximum
35.0 A maximum
35.0 A maximum
668 W maximum
1337 W maximum
1337 W maximum
Breaker (customer provided)
40 A minimum, per installed
module
40 A minimum, per installed
module
40 A minimum, per installed
module
Output (per module)
Output Voltage
Output Current
5 A
ac
maximum
10 A
ac
maximum
5 A
ac
maximum
Output VA
600 VA maximum
1200 VA maximum
Total Harmonic Distortion
(THD)
2 % maximum
Regulation
Environmental
314 BTU/hr
778 BTU/hr
778 BTU/hr
Temperature
Mechanical
Weight
6.5 lb
Cooling
Front to rear forced air