1MAC052634-MB D
Section 3
Vendor-specific implementation
615/620 series ANSI
37
Communication Protocol Manual
Extended event record structure
Table 28:
Extended event record structure with the maximum of 10 event records
Address
1
Register
Values
Description
4xxxx
Num of records
1...10
Write: Number of Event
structures
4xxxx + 1
Selection
Write: Selection code
4xxxx + 2
Sequence Number 1
Event record 1
4xxxx + 3
Unread records left 1
4xxxx + 4
TimeStamp 1
4xxxx + 5
TimeStamp 1
4xxxx + 6
TimeStamp 1
4xxxx + 7
TimeStamp 1
4xxxx + 8
Event Type 1
4xxxx + 9
Data Object Id 1_1
4xxxx + 10
Data Object Id 2_1
4xxxx + 11
Data Value 1
4xxxx + 12
Data Value 1
4xxxx + 13
Sequence Number 2
Event record 2
:
:
:
4xxxx + 23
Data Value 2
4xxxx + 24
Sequence Number 3
Event record 3
:
:
:
4xxxx + 34
Data Value 3
4xxxx + 35
Sequence Number 4
Event record 4
:
:
:
4xxxx + 45
Data Value 4
4xxxx + 46
Sequence Number 5
Event record 5
:
:
:
4xxxx + 56
Data Value 5
4xxxx + 57
Sequence Number 6
Event record 6
:
:
:
4xxxx + 67
Data Value 6
4xxxx + 68
Sequence Number 7
Event record 7
:
:
:
4xxxx + 78
Data Value 7
4xxxx + 79
Sequence Number 8
Event record 8
:
:
:
4xxxx + 89
Data Value 8
4xxxx + 90
Sequence Number 9
Event record 9
:
:
:
4xxxx + 100
Data Value 9
Summary of Contents for 620 Series ANSI