Section 4
1MAC052634-MB D
Modbus parameters and diagnostics
48
615/620 series ANSI
Communication Protocol Manual
TCPWriteAuthority
0=No clients
1=Reg. clients
2=All clients
2=All clients
Write authority
setting for Modbus
TCP/IP clients
EventID
0=Address
1=UID
0=Address
Event ID selection
TimeFormat
0=UTC
1=Local
1=Local
Time format for
Modbus time stamps
ClientIP1
000.000.000.000
Modbus Registered
Client 1
ClientIP2
000.000.000.000
Modbus Registered
Client 2
ClientIP3
000.000.000.000
Modbus Registered
Client 3
ClientIP4
000.000.000.000
Modbus Registered
Client 4
ClientIP5
000.000.000.000
Modbus Registered
Client 5
CtlStructPWd1
****
Password for
Modbus control
struct 1
1
CtlStructPWd2
****
Password for
Modbus control
struct 2
CtlStructPWd3
****
Password for
Modbus control
struct 3
CtlStructPWd4
****
Password for
Modbus control
struct 4
CtlStructPWd5
****
Password for
Modbus control
struct 5
CtlStructPWd6
****
Password for
Modbus control
struct 6
CtlStructPWd7
****
Password for
Modbus control
struct 7
CtlStructPWd8
****
Password for
Modbus control
struct 8
Internal Overflow
0=False
1=True
0=False
Modbus Internal
Overflow:
TRUE-System level
overflow occurred
(indication only)
1. The amount of available control structures may vary depending on the IED type.
Parameter
Values (Range)
Unit
Step
Default
Description