Connecting the inverter inputs
Connect all inverter power cables in the AC cabinet. See details of station type and
corresponding inverter type in below table.
Inverter type
Station type
PVS-100
PVS-100-MVCS
PVS-120
PVS-120-MVCS
To connect the inverter inputs, follow the instructions below:
1.
Make sure that all cables have the maximum cable size = 185 mm
2
.
2.
Considering the AC cable sizes and that the cables must be aligned with the fuse bases,
mark the LV AC lead through holes in the cable cover:
3.
Remove the cable entry covers.
Electrical installation 43