364Ax-Gx Instruction Manual
36
Display indication
Description
Level
Type
Message
Set the Message value in the transmitter database
Utility
ASCII String
Polling Address
Set the Polling Address value in the transmitter
database
Utility
Enumerated
Calibrate
This function provides all the Calibration settings
Main Menu
Sensor Trim
This function provides the trimming of the sensor
Sub Menu
Lower sensor trim
Set the lower Sensor Trim point
Utility
Numerical
Upper sensor trim
Set the upper Sensor Trim point
Utility
Numerical
Output Trim
This function provides all the trimming of the
current output
Sub Menu
Set 4 mA
Trim the output current to 4 mA when the action is
performed
Utility
Numerical
Set 20 mA
Trim the output current to 20 mA when the action is
performed
Utility
Numerical
Reset to Factory Trim
Set the output current Trim and the Sensor Trim at
the Calibration performed in the factory during the
trasmitter manufacturing
Utility
Enumerated
Diagnostics
This function provides all the Diagnostics
information
Main Menu
Diagnostics
This function provides all the Main Diagnostics
information
Sub Menu
PV
Monitor the PV value
Utility
Numerical
HART Eng. Output
Monitor the HART Engineering Output value
Utility
Numerical
Output current
Monitor the Current Output value
Utility
Numerical
Output %
Monitor the Percentage Output value
Utility
Numerical
Sensor temperature
Monitor the Sensor temperature value
Utility
Numerical
Loop Test
This function provides to force the output current at
a specific value
Sub Menu
Set 4 mA
Set the output to 4 mA
Utility
Auto Adjust
Set 20 mA
Set the output current to 20 mA
Utility
Auto Adjust
Set custom value
Set the output current to a defined value
Utility
Manual Adjust