The switchgear must be installed in switchgear cubicles complying with
degree of protection IP 32, IP 43 or IP 54, depending on the prevailing
environmental conditions.
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, actuators and signaling components. It
is the responsibility of each company to conduct its own evalution of the effecti-
veness of the safety system by trained individuals. ABB AG, its subsidiaries and
affiliates (collectively "ABB") are not in a position to evaluate all of the charac-
teristics of a given system or product or machine not designed by
ABB.
Siemens accepts no liability for any recommendation that may be implied or
stated herein. The warranty contained in the contract of sale by ABB is the sole
warranty of ABB. Any statements contained herein do not create new warranties
or modify existing ones.
The C6701 safety combination can be used in EMERGENCY STOP devices accor-
ding to EN 418 and in safety circuits according to EN 60 204-1 (11.98), e.g. in
movable guards and protective doors or in non-contact protective devices in
accordance with IEC 61496-1 (06.98), electrical equipment for furnaces in accor-
dance with DIN VDE 0116 (10.98) and automatic firing systems for gas burners in
accordance with DIN EN 298 (02.94). Depending on the external circuit ele-
ments, safety category 4 according to DIN EN 954-1 or SIL 3 according to
IEC 61508 can be achieved.
The C6701 safety combination has two reliable solid-state outputs. Three LEDs
indicate the operating state and the function.
When the device is put into operation it runs through a self-test to test the
correct functioning of the internal electronics. All internal circuit components
are monitored for faults cyclically during operation.
Connect the EMERGENCY STOP button and/or the position switches or light
arrays to terminals Y11, Y12 and Y21, Y22. Connect the ON button in series with
the NC contacts of the external actuators to the supply voltage L+ (24 V DC) and
to terminal Y34. Connect cascading input 1 either via a safe output or directly to
the supply voltage L+ (24 V DC).
External actuators or loads can be switched via safe outputs 14, 24. It must be
ensured that the actuators or loads and the C6701 electronic safety combination
have the same frame potential. Paralleling outputs 14 and 24 to increase the
load current is not permissible.
If electronic sensors (e.g. light-array monitoring) are used, and in single-channel
operation, Y35 must be connected to L+ (24 V DC). For autostart operation, Y32
must be connected directly to L+ (24 V DC) and Y34 must be connected to it via
NC contacts of the external actuators.
Use a power pack to IEC 60536 safety class III (SELV or PELV)
for power supply!
1)
Sensor circuits open; Cross-circuit between the sensors; Short-circuit of sensors
to frame
2)
only when using circuit variant with "cross-circuit detection"
For further data and accessories see in Main Catalog, part 1.
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
AND BURNS.
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
IMPORTANT NOTICE
Application
Functional description and instructions for connection
Terminal
assignments
Operating
voltage
A1
A2
L+
M
Sensors
Y11, 12
Y21, 22
Y35
Y32
Y34
Channel 1 EMERGENCY STOP or
position switch
Channel 2 EMERGENCY STOP or
position switch
With / without cross-circuit detection
Autostart changeover switch
ON button, feedback circuit
Input
1
Cascading input
Outputs
14, 24
Safe Solid-state outputs
Cable lengths
for 2 x 1.5 mm
2
max. 2000 m (total cable length for sensors)
Figures
Fig. I:
Fig. Ia:
Fig. II:
Fig. III:
Fig. IV:
Fig. V:
Fig. VI:
Fig. VII:
Fig. VIII:
Fig. IX:
Dimension drawings (dimensions in mm)
Terminal designation
Installation
Internal circuit:
¿
power pack,
À
sensors,
Á
Output 1,
Â
Output 2
Protective-door monitoring, two-channel, autostart, category 4 / SIL 3
EMERGENCY STOP, single-channel, monitored start category 2 / SIL 1
EMERGENCY STOP, two-channel, monitored start with additional ON button
category 4 / SIL 3
Light-array monitoring, two-channel, autostart, category 4 / SIL 3
EMERGENCY STOP, two-channel, monitored start with additional ON button
and protective-door monitoring, autostart, category 4 SIL 3
Safety mat, two-channel, autostart, category 3 SIL 2
Operating states
LEDs
Operation
POWER RUN
FAIL
PS
EMERGENCY
STOP
ON button
Outputs
ON
not activated activated
on
activated
1)
not activated off
not activated not activated off
flashes
on startup self-test approx. 7 sec.
Faults
flashes
• Defect in electronics
• Change in terminal assignment
during operation
• Short-circuit to 24V
2)
off
No supply voltage
Fault
clearance
1. Switch supply voltage off.
2. Clear fault or replace device.
3. Switch supply voltage back on.
Technical data
Permissible ambient temperature T
u
Operation/storage
-25 to +60 °C/-40 to +80 °C
Degree of protection to EN 60 529
IP 40, IP 20 at terminals
Rated insulation voltage
50 V
Rated impulse withstand voltage
2 kV
Rated control supply voltage
24 V DC
Rated power
1.3 W
Operating range
0.9 to 1.15 x U
s
Shock resistance (half-sine) as per IEC 60068
8
g
/10 ms
Weight
150 g
Recovery time after EMERGENCY STOP
min. 30 ms
Recovery time after power failure
7 s
Release time after EMERGENCY STOP
30 ms
Pickup time
max. 40 ms
Short-circuit protection
no fusing necessary!
Utilization category
as per IEC 60947-5-1
Rated operational
voltage
[V]
Rated operational current
per output [A]
DC-13
24 2.0
2
Safety combination
C6701
IEC 60 439-1 (1999)
Instructions
Order No.: 2CDC 114002 M4401
English