Appendix C MODBUS® register lists
90 |
266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
Register Address
Data
Type
Object description
Read/
Write
Added
Ext.
32 bit
16 bit
5561
5081
–5082
F
Transducer Temperature Maximum ever measured value
RO
√
5562
5083
–5084
F
Transducer Temperature Minimum ever measured value
RO
√
5563
5085
–5086
F
RTD Maximum ever measured value
RO
√
5564
5087
–5088
F
RTD Minimum ever measured value
RO
√
Customer Operating Range Alarm Levels
5565
5089- 5090
F
DP Above URV Alarm Set at this level (in DP units) referenced to register 5541
=’s URV + ((URV-LRV) * DPHysteresis * 0.01 )
RO
√
5566
5091- 5092
F
DP Below LRV Alarm Set at this level (in DP units) referenced to register 5542
=’s LRV - ((URV-LRV) * DPHysteresis * 0.01)
RO
√
5567
5093-5094
F
DP Below URV Alarm Clears at this level (in DP units) referenced to register 5541
=’s URV - ((URV-LRV) * DPHysteresis * 0.01 / 2)
RO
√
5568
5095-5096
F
DP Above LRV Alarm Clears at this level (in DP Units) referenced to register 5542
=’s LRV + ((URV-LRV) * DPHysteresis * 0.01 / 2)
RO
√
5569
5097-5098
F
DP Alarm Hysteresis Percent of User Range Span referenced to register 5541 &
5542 (default 2%)
(DPHysteresis)
RO
√
5570
5099-5100
F
SP Alarm Hysteresis Percent of User Range Span referenced to register 5543 &
5544 (default 2%)
(SPHysteresis)
RO
√
5571
5101-5102
F
SP Above URV Alarm Set at this level (in SP units) referenced to register 5543
=’s URV + ((URV-LRV) * SPHysteresis * 0.01 )
RO
√
5572
5103-5104
F
SP Below LRV Alarm Set at this level (in SP units) referenced to register 5544
=’s URV - ((URV-LRV) * SPHysteresis * 0.01 )
RO
√
5573
5105-5106
F
SP Below URV Alarm Clears at this level (in SP units) referenced to register 5543
=’s LRV - ((URV-LRV) * SPHysteresis * 0.01 / 2)
RO
√
5574
5107-5108
F
SP Above LRV Alarm Clears at this level (in Sp Units) referenced to register 5544
=’s LRV + ((URV-LRV) * SPHysteresis * 0.01 / 2)
RO
√
Measurements Bias Parameters
5575
5109-5110
F
DP bias value is being added to the DP measurement producing an overall offset
adjustment.
RO
√
5576
5111
– 5112
F
SP bias, see preceding register for discussion.
RO
√
5577
5113
– 5114
F
Set DP to a value, units are same as the DP measurement.
DP bias = value
– current measurement.
This results in the reported value in register 401-402 to be the value.
R/W
√
5578
5115
– 5116
F
Set SP to value, see preceding register for discussion.
R/W
√
5579
5117
x
Reset DP Bias, sets the bias value to zero, effectively removing any effects of bias
on DP measurement.
This is an action register and the data value has no meaning.
WO
√
5580
5118
x
Reset SP Bias, sets the bias value to zero, see preceding register.
WO
√
Informative / Maintenance (Available in all Modbus mapping modes)
64001
64001
U8
Modbus mapping selection:
0 = ABB map
1 = Rosemont map
2 = Invensys map
RO
√
64002
64002-
64003
U32
Date and time the CB firmware was built. Julian date number of seconds since Jan
01, 1970 00:00:00
RO
√