90 OI/266/FF/ADD-EN Rev. B
| 2600T Series Pressure transmitters
266 Models - FOUNDATION Fieldbus
Linear volume measurement setting
Process Info
Device parameter to be configured
TAG
PD_TAG
Calibration Lower Range Value 0%
PRTB_PRIMARY_VALUE_RANGE_ 0% AI1_XD_SCALE 0%
Calibration Upper Range Value 100%
PRTB_PRIMARY_VALUE_RANGE _100% AI1_XD_SCALE 100%
Calibration Unit
PRTB_PRIMARY_VALUE_RANGE _UNIT AI1_XD_SCALE_UNIT
Linearization Type
AI1_L_TYPE = Indirect
Output scale 0%
AI1_OUT_SCALE 0%
Output scale 100%
AI1_OUT_SCALE 100%
Output Scale Unit
AI1_OUT_SCALE Unit Code
AI1_CHANNEL = 1
Special volume measurement setting
Process Info
Device parameter to be configured
TAG
PD_TAG
Calibration Lower Range Value 0%
PRTB_PRIMARY_VALUE_RANGE_ 0%
Calibration Upper Range Value 100%
PRTB_PRIMARY_VALUE_RANGE _100%
Calibration Unit
PRTB_PRIMARY_VALUE_RANGE _UNIT
Linearization Type
QUATERNARY_VALUE_ LIN_TYPE
Linear
cylindrical lying container
spherical container
Output scale 0%
AI1_OUT_SCALE 0%
Output scale 100%
AI1_OUT_SCALE 100%
Output Scale Unit
AI1_OUT_SCALE Unit Code
AI1_CHANNEL = 4
AI1_L_TYPE = Indirect
AI1_XD_XCALE = 0.0 ... 100.0 / %
Further common setting
Process Info
Device parameter to be configured
Node Address
Damping
AI1_PV_FTIME
Critical Limit Low
AI1_LO_LO_LIM
Advisory Limit Low
AI1_LO_LIM
Advisory Limit High
AI1_HI_LIM
Critical Limit High
AI1_HI_HI_LIM
Alarm Hysteresis
AI1_ALARM_HYS
No field calibration is normally requested, the transmitter has been trimmed to the calibration points (URV and LRV) to provide the
best performances in the real operating range.
Important
In case the calibrated range has to be changed, please refer to the section “Sensor Calibration” in this manual