2600T Series Pressure transmitters |
OI/266/FF/ADD-EN Rev. B 45
Idx
Parameter
Data
Type
Size
Storage
Description / Range / Selections / Note
33
ROUT_IN
RW
R
DS-65
5
N
Expr
essed in
OUT_SCALE Unit
Used when the mode is ROUT
.
Target output value pr
ovided by a supervisory host
34
SHED_OPT
RW
S
U8
1
S
Define actions to be taken on r
emote contr
ol device timeout
35
RCAS_OUT
R
R
DS-65
5
D
Expr
essed in
PV_SCALE Unit.
Used when mode is RCAS.
Block setpoint V
alue after ramping – pr
ovided by a supervisory host for back calcula
-
tions and to allow action to be taken under limiting conditions or mode change
36
ROUT_OUT
R
R
DS-65
5
D
Expr
essed in
OUT_SCALE Unit.
Used when mode is ROUT
.
Block output V
alue pr
ovided to a supervisory host for a back calculation to allow
action to be taken under limiting conditions or mode change
37
TRK_SCALE
RW
R
DS-68
11
S
The high and low scale values, engineering units code, and number of digits to the right of the decimal point, associated with
TRK_V
AL
.
38
TRK_IN_D
RW
R
DS-66
2
N
This discr
ete input is used to initiate exter
nal tracking of the block output to the value specified by TRK_V
AL.
39
TRK_V
AL
RW
R
DS-65
5
N
Expr
essed in
TRK_SCALE Unit
.
This input is used as the track value when exter
nal tracking is enabled by TRK_IN_D.
40
FF_V
AL
RW
R
DS-65
5
N
Expr
essed in FF_SCALE Unit.
The feed forwar
d value and status
41
FF_SCALE
RW
R
DS-68
11
S
The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with F
F_V
AL
42
FF_GAIN
RW
S
FLT
4
S
The gain that the feed forwar
d inpt is multiplied by befor
e it is added to the calculated contr
ol output.
43
UPDA
TE_EVT
R
R
DS-73
14
D
This alert is generated by any change to the static data
44
BLOCK_ALM
RW
R
DS-72
13
D
The block alarm is used for all configuration, har
dwar
e, connection failur
e or system pr
oblems in the block. The cause of the alert is
enter
ed in the subcode field. The first alert to become active will set the Active Status in the status parameter
. As soon as the Unr
e-
ported status is clear
ed by the alert r
eporting task, another block alert may be r
eported without clearing the Active Status, if the
subcode has changed
45
ALARM_SUM
RW
R
DS-74
8
mix
The summary alarm is used for all pr
ocess alarm in the block. The cause of the alert is enter
ed in the subcode field. The first
alert to become active will set the Active Status in the status parameter
. As soon as the Unr
eported status is clear
ed by the
alert r
eporting task, another block alert may be r
eported without clearing the Actve Status, if the subcode has changed.
46
ACK_OPTION
RW
S
B_STR
2
S
Used to set auto acknowledgment of the alarms
47
ALARM_HYS
RW
S
FLT
4
S
Alarm Hyster
esis is the amount the PV must
retur
n within the alarm limit befor
e the alarm con
-
dition clears.
0 or > 0 expr
essed as per
cent of the
OUT_SCALE
span (default =[0.5%])
48
HI_HI_PRI
RW
S
U8
1
S
0 - 15
Expr
essed in
OUT_SCALE unit.
49
HI_HI_LIM
RW
S
FLT
4
S
Critical Limit High pr
oducing the High-High Alarm
50
HI_PRI
RW
S
U8
1
S
0 - 15
51
HI_LIM
RW
S
FLT
4
S
Advisory Limit High pr
oducing the High Alarm
52
LO_PRI
RW
S
U8
1
S
0 - 15
53
LO_LIM
RW
S
FLT
4
S
Advisory Limit Low pr
oducing the Low Alarm
54
LO_LO_PRI
RW
S
U8
1
S
0 – 15
55
LO_LO_LIM
RW
S
FLT
4
S
Critical Limit Low pr
oducing the Low-Low Alarm
56
DV_HI_PRI
RW
S
U8
1
S
0 - 15
57
DV_HI_LIM
RW
S
FLT
4
S
Deviation High Limit pr
oducing the Deviation
High Alarm
58
DV_LO_PRI
RW
S
U8
1
S
0 - 15
59
DV_LO_LIM
RW
S
FLT
4
S
Deviation Low Limit pr
oducing the Deviation Low
Alarm
60
HI_HI_ALM
RW
R
DS-71
16
D
High-High Alarm
61
HI_ALM
RW
R
DS-71
16
D
High Alarm