2600T Series Pressure transmitters |
OI/266/FF/ADD-EN Rev. B 51
Idx
Parameter
Data
Type
Size
Storage
Description / Range / Selections / Note
21
BIAS_IN_1
RW
S
FLT
4
S
The constant to be added to IN_1
22
GAIN_IN_1
RW
S
FLT
4
S
The constant to be multiplied times (IN_1 + Bias)
23
BIAS_IN_2
RW
S
FLT
4
S
The constant to be added to IN_2
24
GAIN_IN_2
RW
S
FLT
4
S
The constant to be multiplied times (IN_2 + Bias)
25
BIAS_IN_3
RW
S
FLT
4
S
The constant to be added to IN_3
26
GAIN_IN_3
RW
S
FLT
4
S
The constant to be multiplied times (IN_3 + Bias)
27
COMP_HI_LIM
RW
S
FLT
4
S
The high limit imposed on the PV compensation term. Expr
essed in PV_SCALE Unit Code
28
COMP_LO_LIM
RW
S
FLT
4
S
The low limit imposed on the PV compensation term. Expr
essed in PV_SCALE Unit Code
29
AR
TH_TYPE
RW
S
U8
1
S
The identification number of the arithmetic algorithm
1
Flow Compensation, Linear
2
Flow Compensation, Squar
e Root
3
Flow Compensation, Appr
oximate
4
BTU Flow
5
Traditional Multiple Divide
6
A
verage
7
Traditional Summer
8
Fourth Or
der Polynomial
9
Simple HTG compensated Level
30
BAL_TIME
RW
S
FLT
4
S
Acceptable value:
OUT_SCALE
+/- 10%
Expr
essed in
OUT_SCALE Unit
The specified time for the inter
nal working value of bias to r
etur
n to operator set bias. Also
used to specify the time constant at which the integral term will move to obtain balance
when the output is limited and the mode is AUTO, CAS, or RCAS. Expr
essed in seconds
31
BIAS
RW
S
FLT
4
N
Expr
essed in
OUT_SCALE Unit
The bias value used in computing the function block output
32
GAIN
RW
S
FLT
4
S
0 or > 0
Dimensionless value used by the block algorithm in calculating the block output
33
OUT_HI_LIM
RW
S
FLT
4
S
Acceptable value:
OUT_SCALE
+/- 10%
Expr
essed in
OUT_SCALE Unit
Limits the maximum output value.
34
OUT_LO_LIM
RW
S
FLT
4
S
Limits the minimum output value.
35
UPDA
TE_EVT
R
R
DS-73
14
D
This alert is generated by any change to the static data
36
BLOCK_ALM
RW
R
DS-72
13
D
The block alarm is used for all configuration, har
dwar
e, connection failur
e or system pr
oblems in the block. The cause of the alert is enter
ed
in the subcode field. The first alert to become active will set the Active Status in the status parameter
. As soon as the Unr
eported status is
clear
ed by the alert r
eporting task, another block alert may be r
eported without clearing the Active Status, if the subcode has changed