60   OI/266/HART-EN Rev. M 

| 2600T Series Pressure transmitters

8 Operation

For additional information, refer to the operating instructions 
included with the handheld terminal.

If the transmitter has been configured in the factory according 
to customer specifications for the measuring point, all you have 
to do is mount the transmitter as prescribed (to correct 
potential zero shifts, refer to the section “Correcting the zero 
shift”), and switch it on. The measuring point will now be ready 
for use.

If, however, you wish to make changes to the configuration, a 
handheld terminal or - preferably - a graphical user interface 
(DTM) is required. This DTM tool renders the device fully 
configurable. It supports both the HART protocol and 
PROFIBUS PA fieldbus protocol, and can be run on a PC or 
laptop, or as part of an automation system. Where 
FOUNDATION Fieldbus is concerned, the device description 
(DD), which can be loaded onto various configuration tools, is 
required for configuration purposes.

Refer to the installation manual provided with the software for 
the steps required to install the operating tool. The most 
important parameters can be set via the path “Parametrize_
Differential Pressure Measurement”.

The program offers the option of configuring, polling, and 
testing the transmitter. 

In addition, offline configuration can be performed by means of 
an internal database. 

Each configuration step is subject to a plausibility check. You 
can call up context-sensitive help at any time by pressing the 
“F1” key. Immediately after you have received the transmitter or 
before you change the configuration, we recommend that you 
save the existing configuration data to a separate data storage 
medium, via the path “File_Save”.

8.17 Configuration with the graphical user interface 
(DTM) - System requirements

— Operating control program (e.g., ABB Asset Vision Basic 

version 1.00.17 or higher)

— DTM (Device Type Manager; graphical user interface)

— Operating system (depending on the respective control 

program)

To operate the Asset Vision Basic please refer to the relevant 
operating instruction.

8.18 Standard and Advanced HART: functionality

266 Pressure Transmitters can be codified with:

— Advanced HART and 4 to 20 mA

— Standard HART and 4 to 20 mA

— HART and 4 to 20 mA Safety, certified to IEC 61508

Advanced and Standard HART feature some differencies in 
terms of functionality.

Functionality

266 Advanced HART 266 Standard HART

Configuration via HMI

On board

Not available

SIL certified

On board

Not available

PILD

On board

On board

Trend

On board

Not available

Totalizer

On board

On board

Service Port

On board

Not available

Electronic replacement

On board

Not available

8.19 Advanced HART software revision history

Revision

Description

Release 

date

From To

7.1.11 First release

09/2009

7.1.11 7.1.12

Bug Fixing: 

—  microbar and millitor units added
—  HART command 35 bug fixed. By HART 

specificaiton #35 unit should not be set pv unit

—  if the local indicator was not mounted, only 

one operation via push buttons was performed

—  MWP diagnosis classification become 

Maintenance instead of Off-Specification

Improvements: 

—  replacement functionality improved
—  internal improvements to reduce factory 

configuration

—  more/stronger checks about process variables 

goodness

—  HART response time reduced (30%)

06/2010

7.1.12 7.1.14

Improvements:

—  factory configuration speeded up
—  service detailed diagnosis implemented

01/2011

7.1.14 7.1.15

Bug Fixing: 

—  sensor trimming via local display was 

performend only in kPa

—  diagnosis “Replace Error” no more shown
—  unit strings on display (Nm3, bbl, t) were wrong

New Features: 

—  new language (French & Spanish) on local 

indicator

—  sensor polarity invertion

01/2013

7.1.15 7.2.1

HART 7 implementation

11/2015

7.1.15

7.2.1

7.1.16
(HART 5)
 7.2.2
(HART 7)

New Features: 

—  Temperature alarm enabled by user
—  oscillation alarm control
—  switching of alarm for wrong power supply

10/2018

8.20 Standard HART software revision history

Revision

Description

Release 

date

From

To

7.1.50 First release

02/2013

7.1.51 Internal release not published
7.1.52 Internal release not published

7.1.52 7.1.53

Bug Fixing:

—  HART burst mode
—  correcting Custom unit visualization on LCD

Improvements: 

—  boot loader performance
—  HART secondary response code
—  Electronics temperature reading

01/2014

7.1.53 7.1.54

Integrated LCD firmware integration 

07/2014

7.1.54 7.1.55

Bug fixing on EEPROM

10/2014

7.1.55 7.1.56

Obsolete Microprocessor replacement

06/2016

7.1.56 7.2.50

HART 7 Introduction

10/2016

7.1.56 7.1.74

(HART 5)

Several bug fixing

10/2018

7.2.50 7.2.54

(HART 7)

Several bug fixing and certification
HART burst mode removed

Intermediate releases for internal tests not published  

Summary of Contents for 266 HART Series

Page 1: ...prehensive range of top quality pressure measurement products specifically designed to meet the widest range of applications ranging from arduous conditions in offshore oil and gas to the laboratory e...

Page 2: ...ns As a part of ABB a world leader in process automation technology we offer customers application expertise service and support worldwide We are committed to teamwork high quality manufacturing advan...

Page 3: ...RST 266DRH 266MRT 266RRT 13 5 5 1 Bracket mounting optional 14 5 5 2 B2 Pipe and wall mounting bracket details 17 5 5 3 B5 Flat type bracket details 18 5 6 Mounting a P style pressure transmitter 19 5...

Page 4: ...tructure 38 8 13 1 Easy Set up Standard HART version 40 8 13 2 Easy Set up Advanced and Safety HART version 41 8 13 3 Device Set up 42 8 13 4 Display 46 8 13 5 Process Alarm 50 8 13 6 Calibrate 51 8 1...

Page 5: ...to the troubleshooting and maintenance operations 1 2 Models covered by this manual The present manual can be used for all the 266 models with exception done for the 266Cxx and 266Jxx multivariable ve...

Page 6: ...quate safety systems For safety reasons ABB draws your attention to the fact that only sufficiently insulated tools conforming to EN 60900 may be used Since the transmitter may form part of a safety c...

Page 7: ...012 19 EU or corresponding national laws Starting from August 15th 2018 electrical and electronic equipment marked with the crossed out wheeled bin symbol may not be disposed as unsorted municipal was...

Page 8: ...components Figure 2 Gauge absolute pressure transmitter components 2 Important These two pictures show only two different kinds of transmitters equipped with Barrel type housing Please consider that...

Page 9: ...nsor The lowest value of the measured value that the transmitter can be adjusted to measure URV Upper Range Value The highest value of the measured value to which the transmitter is calibrated LRV Low...

Page 10: ...er supply output signal diaphragms material fill fluid range limit serial number maximum process working pressure PS and temperature TS The Tag plate instead provides customer tag number and calibrate...

Page 11: ...l wire AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD Figure 4 4 line layout of the optional wired on Stainless Ste...

Page 12: ...specifically powerful jets of water under standardized conditions 7 means that the housing is protected against water specifically against the effects of temporary immersion in water under standardize...

Page 13: ...read the following considerations on the Vent Drain valves in the following relevant paragraph Attention Potential damage to transmitter In case of a High Static differential pressure transmitter 266D...

Page 14: ...11 0 43 113 4 45 72 2 83 66 2 60 with plug 78 3 07 with d v valve 58 2 28 55 2 17 Figure 7 Differential Pressure Style transmitter with barrel housing installed on a horizontal pipe with optional brac...

Page 15: ...e 58 2 28 55 2 17 Figure 9 Differential Pressure Style transmitter with barrel housing installed on a vertical pipe with optional bracket B2 129 5 06 197 7 73 72 2 83 116 4 57 136 5 35 178 6 99 183 7...

Page 16: ...Pressure Style transmitter with barrel housing and Kynar inserts installed on a horizontal pipe with optional bracket B2 91 3 58 179 7 02 54 2 13 116 4 57 29 1 14 18 0 71 113 4 45 72 2 83 210 8 28 18...

Page 17: ...8 2 28 210 8 28 113 4 45 72 2 83 Figure 13 Differential Pressure Style transmitter with barrel housing and Kynar inserts installed on a vertical pipe with optional bracket B2 5 5 2 B2 Pipe and wall mo...

Page 18: ...71 11 0 43 210 8 28 58 2 28 55 2 17 95 3 72 174 6 86 Figure 15 Differential Pressure Style transmitter with barrel housing installed on a box pipe with optional bracket for SST housing B5 5 5 3 B5 Fl...

Page 19: ...he filling liquid exerts hydrostatic pressure on the measuring diaphragm resulting in a zero shift In such an event the zero point can be corrected via the zero push button or via the set PV to zero c...

Page 20: ...4 12 116 4 57 72 2 83 283 11 12 27 1 06 width across flats of exagon Figure 19 Model 266H or 266N High overload resistant P Style transmitter with sensor Z with barrel housing installed on a 2 pipe w...

Page 21: ...60 30 1 19 72 2 83 11 0 43 128 5 04 85 3 35 18 0 71 145 5 71 54 2 13 65 2 56 39 1 54 16 0 63 18 0 71 72 2 83 49 1 93 105 4 13 32 1 26 width across flats of exagon Figure 22 Model 266H or 266N Hi over...

Page 22: ...19 11 0 43 22 0 87 width across flats of exagon Figure 23 Model 266G or 266A P Style transmitter with DIN housing installed on a 2 pipe with optional bracket B7 Stainless Steel 316L Figure 24 Pipe an...

Page 23: ...better yet flushed through with the measuring medium before connection Where a fluid vaporous measuring medium is being used the liquid in both measuring pipes must be at the same level If a separati...

Page 24: ...x 266Rxx and for PTFE O rings pretightening hand tight Pretightening to 10 Nm Final tightening to 50 Nm For model 266PSx 266VSx and 266RSx it is only possible to have one adapter with low pressure sid...

Page 25: ...ment Place the taps to the top or side of the line Mount the transmitter above the taps The process fluid must enter the transmitter primary 1 Open equalizing valve C 2 Close low pressure B and high p...

Page 26: ...ed Connect the H side of the transmitter to the bottom of the tank Connect the L side of the transmitter to the upper part of the tank Fill the vertical section of the connecting line to the upper par...

Page 27: ...Connect the transmitter to the tank Figure 36 Gauge or absolute pressure measurement on a tank 5 14 7 Pressure or absolute pressure measurement of a liquid in a pipe Place the tap at the side of the...

Page 28: ...to the pipe Fill the vertical section of the connecting line to the tap with a compatible liquid through the dedicated filling tee Figure 38 Gauge or absolute pressure measurement of condensable vapo...

Page 29: ...ONF 2 1 1 2 5 4 3 6 HART hand held communicator may be connected at any wiring termination point in the loop providing the minimum resistance is 250 ohm If this is less than 250 ohm additional resista...

Page 30: ...transmitter operates from 10 5 to 42 V DC with no load and is protected against reverse polarity connection For Ex ia and other intrinsically safe approval power supply must not exceed 30 V DC Minimum...

Page 31: ...g ring 6 PG 11 set screw 7 Cable diameter 5 11 mm or 0 20 0 43 inch 6 6 Grounding Pressure transmitter housing should be grounded or earthed in accordance with national and local electrical codes Grou...

Page 32: ...ee figure 3 at chapter 4 by releasing the holding screw lying on the bottom left corner Use a suitable screwdriver to press the switch down fully Then turn the switch clockwise by 90 Important To deac...

Page 33: ...nstruments do not feature the external non intrusive Zero Span and Write Protection push buttons To activate this function it is necessary to proceed as detailed below Remove instrument cover and the...

Page 34: ...o and Span buttons On the right is the version if selecting option R1 without on board buttons which are functionally replaced by the Z and S push buttons located under the nameplate with dip switch 3...

Page 35: ...ormation The tag plate contains information on the lower range value and upper range value set In general the following applies The first pressure value e g 0 mbar is always assigned to the 4 mA signa...

Page 36: ...iated to B and R letters in the lower corners as shown in figure 48b Important For Standard HART version after releasing Z and S buttons on LCD or external during range values configuration or PV to z...

Page 37: ...transmitter In addition diagnostic information is provided To access the functionality of the HMI an activation procedure needs to be carried out The keypad activation procedure is different between...

Page 38: ...The last selectable sub menu allows user to reset all the parameters to the default configuration 8 10 LCD L1 and LS option activation considerations Gain access to the display by unscrewing the windo...

Page 39: ...ctions relevant to the display itself The menu driven structure will guide you through the choice of some functional aspects as the display language and contrast Moreover it is possible to choose in d...

Page 40: ...40 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 1 Easy Set up Standard HART version...

Page 41: ...4 key and set LRV value After entering the settings press the 1 key to move to the next menu item Press the 4 key and select the transfer function from the list with 2 3 After entering the settings pr...

Page 42: ...42 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 3 Device Set up...

Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 43 8 Operation...

Page 44: ...44 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...

Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 45 8 Operation...

Page 46: ...46 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 4 Display...

Page 47: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 47 8 Operation...

Page 48: ...48 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...

Page 49: ...limit which is configurable in case the PV will be above the URV upper range value the signal will be driven to the High Saturation limit which is configurable too In case the transmitter diagnostic...

Page 50: ...50 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 6 Calibrate...

Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 51 8 Operation 8 13 7 Totalizer...

Page 52: ...52 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...

Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 53 8 Operation...

Page 54: ...54 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 8 Diagnostics...

Page 55: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 55 8 Operation 8 13 9 Device Info...

Page 56: ...56 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 10 Communication...

Page 57: ...ch triangular weir Bidirectional Flow Custom linearization table Cylindrical lying tank Spherical tank These output functions can be activated using a Configuration Tool Digital LCD Integral Display H...

Page 58: ...function it is used typically for volumetric level measurement in tanks with an irregular shape It can be registered to a freely identifiable transfer function with a maximum of 22 base points The fi...

Page 59: ...nnection examples with communication resistor in the connection line The 266 transmitters can be configured by either one of the following device Hand Held terminals like the ABB 691HT ABB DHH800 MFC...

Page 60: ...HART and 4 to 20 mA Safety certified to IEC 61508 Advanced and Standard HART feature some differencies in terms of functionality Functionality 266 Advanced HART 266 Standard HART Configuration via HM...

Page 61: ...be broken or not correctly calibrated A DAC digital to outpt converter trimming should be performed and if the error persists the communication board must be replaced Analog Signal to Alarm M030 020 E...

Page 62: ...de Remove the input simulation no effect C088 030 Input Simulation Active The Static Pressure Value produced in output is derived by the value simulated in input Use a HART configurator DTM Hand held...

Page 63: ...eeds the limit of the sensor Exceeding the Static Pressure can reduce accuracy mechanically damage the diaphragm and may require calibration replacement An incorrect transducer model could have been s...

Page 64: ...instructions in the sections Safety and Electrical connection and perform the steps outlined there in reverse order 10 2 Pressure transmitter sensor Essentially maintenance is not required for the tra...

Page 65: ...the pressure transducer needs to be replaced proceed as follows 1 Insulate the transmitter from the process by acting on the manifolds or on the insulation valves 2 Open the vent valves to allow senso...

Page 66: ...o 50 mm depth Application with Gas Application with Dust Note the transmitter must be connected to a supply associated apparatus certified Ex ia Note the protection is mainly assured by the IP degree...

Page 67: ...sured by the IP degree associated to the low power from supply This can either be ia or ib Zone 0 Zone 1 Dangerous medium process Tank Zone 0 Zone 1 sepa ration element Primary transducer 266 Tx Categ...

Page 68: ...ral indicates the protection of the inside electronics against ingress of water The assigned 7 means an enclosure water protected against a temporary immersion in water under standardized conditions o...

Page 69: ...d c max output voltage as above indicated The Ii of the transmitter is less than 25 mA Zone 2 266 Tx Category 3Gc Ex ic Note the protection is mainly assured by the IP degree associated to the low pow...

Page 70: ...lectrical Equipment FM 3810 Electrical and Electronic Test Measuring and Process Control Equipment NEMA 250 Enclosure for Electrical Equipment 1000 Volts Maximum 11 2 2 Classifications The 2600T Serie...

Page 71: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 71...

Page 72: ...72 OI 266 HART EN Rev M 2600T Series Pressure transmitters...

Page 73: ...nsmitters ABB s portfolio of device management Fieldbus and wireless solutions Scalable asset device management Asset vision software Mobility handhelds Customer support We provide a comprehensive aft...

Page 74: ...74 OI 266 HART EN Rev M 2600T Series Pressure transmitters Intentionally blank...

Page 75: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 75 Intentionally blank...

Page 76: ...matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB ABB 2018 A...

Reviews: