2600T Series Pressure transmitters |
OI/266/HART-EN Rev. M 31
6 Transmitter wiring
6.5.2 Assembling and connecting the socket connector
The socket connector for connecting the cable is supplied
unassembled as an accessory for the transmitter.
— The contacts (2) are crimped or soldered onto the cable
ends (wire cross section of 0.75 … 1 mm² (AWG 18 …
AWG 17)), from which approx. 1.5 … 2 cm (0.59 …
0.79 inch) of the sleeve and approx. 8 mm (0.32 inch) of
the insulation have been stripped; they are then inserted
into the socket (1) from the rear.
— Slide the set screw (6), clamping ring (5), gasket (4), and
housing (3) onto the cable in the order indicated before
assembly (you may have to adjust the gasket (4) to fit the
cable diameter).
Important.
Before you press the contacts completely into the
socket, check the connection points again. Incorrectly inserted
contacts can be removed by using a press-out tool (part no.:
0949 813), or a standard ballpoint pen as a makeshift tool. Please
observe the connection diagram included with the plug.
Figure 42: Socket connector components
1 - Socket
2 - Contact
3 - Housing
4 - Gasket (can be cut)
5 - Clamping ring
6 - PG 11 set screw
7 - Cable (diameter 5 - 11 mm or 0.20 - 0.43 inch)
6.6 Grounding
Pressure transmitter housing should be grounded or earthed in
accordance with national and local electrical codes. Ground
connection is mandatory for surge protector equipped devices
in order to ensure proper functioning.
Protective grounding terminals (PE) are available outside and/or
inside the housing of the transmitter. Both ground terminals are
electrically connected and it up to the user to decide which one
to use. The most effective transmitter case grounding method
is direct connection to earth ground with impedance equal or
less of 5 ohm.
Figure 43: Ground connection on transmitter housing
6.7 Surge protector equipped terminal block
(optional)
The pressure transmitter housing with surge protector (code
S2) inside the terminal board must be connected using the
grounding terminal (PE), by means of a short connection with
the equipotential bonding.
Equipotential bonding conductor must to have 4.00mm2 of
maximum cross-section.
Important.
Test voltage withstand capability can no longer be
ensured when this protective circuit is used.
6.8 Common mode voltages
266 pressure transmitter operates within the specified levels of
accuracy for common-mode voltages of up to 250V between
lines and housing grounded.
Summary of Contents for 266 HART Series
Page 42: ...42 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 3 Device Set up...
Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 43 8 Operation...
Page 44: ...44 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 45 8 Operation...
Page 46: ...46 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 4 Display...
Page 47: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 47 8 Operation...
Page 48: ...48 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 50: ...50 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 6 Calibrate...
Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 51 8 Operation 8 13 7 Totalizer...
Page 52: ...52 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 53 8 Operation...
Page 54: ...54 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 8 Diagnostics...
Page 55: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 55 8 Operation 8 13 9 Device Info...
Page 56: ...56 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 10 Communication...
Page 71: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 71...
Page 72: ...72 OI 266 HART EN Rev M 2600T Series Pressure transmitters...
Page 74: ...74 OI 266 HART EN Rev M 2600T Series Pressure transmitters Intentionally blank...
Page 75: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 75 Intentionally blank...