2600T Series Pressure transmitters |
OI/266/HART-EN Rev. M 49
8 Operation
8.13.5 Process Alarm
This menu allows the complete configuration of the analogue output in case of saturation and alarm. The output signal will range
from 4 to 20 mA in case the process variable is within the calibrated span limits. In case the process variable (PV) will be below
the LRV (lower range value) the signal will be driven to the “Low Saturation” limit (which is configurable), in case the PV will be
above the URV (upper range value) the signal will be driven to the “High Saturation” limit (which is configurable too).
In case the transmitter diagnostic detects a failure the signal will be driven upscale or downscale according to the user
preferences (the failure direction is selected via the dip switch 4 and 5 on the communication board). The exact value to which the
signal will be driven can be configured via the above menu (Alarm limits). As a convention the Low Alarm limit must be < the Low
Saturation limit and the High Alarm limit must be > than the High Saturation limit.
Summary of Contents for 266 HART Series
Page 42: ...42 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 3 Device Set up...
Page 43: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 43 8 Operation...
Page 44: ...44 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 45: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 45 8 Operation...
Page 46: ...46 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 4 Display...
Page 47: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 47 8 Operation...
Page 48: ...48 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 50: ...50 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 6 Calibrate...
Page 51: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 51 8 Operation 8 13 7 Totalizer...
Page 52: ...52 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation...
Page 53: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 53 8 Operation...
Page 54: ...54 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 8 Diagnostics...
Page 55: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 55 8 Operation 8 13 9 Device Info...
Page 56: ...56 OI 266 HART EN Rev M 2600T Series Pressure transmitters 8 Operation 8 13 10 Communication...
Page 71: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 71...
Page 72: ...72 OI 266 HART EN Rev M 2600T Series Pressure transmitters...
Page 74: ...74 OI 266 HART EN Rev M 2600T Series Pressure transmitters Intentionally blank...
Page 75: ...2600T Series Pressure transmitters OI 266 HART EN Rev M 75 Intentionally blank...