Configuration
IM/265D/V-EN-02 265Dx,
265VS
47
8.1.3 Transmitter with FOUNDATION Fieldbus communication
Parameters
Factory settings
Measuring profile
Pressure
Physical unit
mbar/bar
Output scale 0 %
Lower range limit (LRL)
Output scale 100 %
Upper range limit (URL)
Output
Linear
Upper alarm limit
Upper range limit (URL)
Upper warning limit
Upper range limit (URL)
Lower warning limit
Lower range limit (LRL)
Lower alarm limit
Lower range limit (LRL)
Hysteresis limit value
0.5 % of output scale
PV filter
0.125 sec.
Address
Not required
Any or all of the configurable parameters listed above - including the lower and upper range
values - can be changed using any FOUNDATION Fieldbus-compatible configuration tool. Data
regarding flange type and material, O-ring materials, and type of filling liquid is stored in the
device.
Pos: 19.5 /Überschriften/1.1/1-spaltig/J - L/Konfigurationsarten @ 0\mod_1140521210140_3101.doc @ 3196
8.2
Configuration types
Pos: 19.6 /Konfiguration, Parametrierung/Druck/Druckmessumformer/Allgemein/Konfigurationsarten @ 2\mod_1150098392546_3101.doc @ 29440
Pressure transmitters can be configured as follows:
• Configuration of the parameters for the lower and upper range values, without an LCD
display
• Configuration of the pressure transmitter using the LCD display (menu-controlled)
• Configuration with a handheld terminal
• Configuration using a PC/laptop via the graphical user interface (DTM)