Configuration
IM/265D/V-EN-02 265Dx,
265VS
49
Configuring the parameters
1.
Apply the pressure for the "lower range value" and wait approx. 30 s until it has stabilized.
2.
Press the 0 % button. This sets the output current to 4 mA.
3.
Apply the pressure for the "upper range value" and wait approx. 30 s until it has stabilized.
4.
Press the 100 % button. This sets the output current to 20 mA.
5.
If required, reset the damping to its original value.
6.
Record the new settings. The respective parameter will be stored in the non-volatile memory
10 s after the 0 % or 100 % button is last pressed.
Warning - Potential damage to parts
Operating the control buttons with a magnetic screwdriver is not permitted.
Important
This configuration procedure only changes the
4 … 20 mA
current signal; it does not affect the
physical process pressure shown on the digital display or user interface. To avoid potential
discrepancies, you can make corrections by following the menu path "Calibrate-Differential
Pressure Measurement-Adjust input" in the user interface.
After performing a correction, you must check the device configuration.