background image

4

6. Always round up to the next whole number. For example, if the minimum requirement is 2.1 units, 3

units are recommended, not 2.

Example 1:

How many 900 CFM units are needed to provide at least 6 ACH in a 25’ x 30’ x 10’ containment area, with a
20% safety factor?
   V = 25 x 30 x 10 = 7,500 Cubic Feet
   Total CFM = (7,500 x 6 x 1.2) 

÷

 60 = 900 CFM

   Minimum # Units Req’d = 900 CFM 

÷

 900 CFM 

(airflow of unit)

 = 

1 Unit  Required

Example 2:

How many 900 CFM units are needed to provide at least 5 ACH in a 50’ x 42’ x 10’ containment area, with a
25% safety factor?

 V = 50 x 42 x 10 = 21,000 Cubic Feet
Total CFM = (21,000 x 5 x 1.25) 

÷

 60 = 2,188 CFM

Minimum # Units = 2,188 

÷

 900 = 2.43 = 

3 Units Required

Note: This example illustrates the importance of a Safety Factor. If no SF were used, only 1,750 CFM (2 units)
would be required.

PRED1200 TRANSPORT

Note

:  The PRED1200 can be transported in the horizontal position.  If extremely poor road conditions exist, or

excessive shock and vibration are expected, take precautionary measures by padding the unit to provide impact
absorption during transport.

Caution

:  Always use caution when moving the PRED1200 inside a building or home.  The unit weighs 70

pounds.  Older structures with weakened floors or staircases may require special considerations for safe transport.

ELECTRICAL REQUIREMENTS

1.   The PRED1200 requires a minimum of 110 volts AC, 60 Hz to operate properly; however, maximum airflow

performance requires 120 volts AC, 60 Hz.

2.   Due to momentary start-up current surge, the unit requires a 15 amp circuit that is free of other loads.
3.   Extension cords used for the PRED1200 must be UL-listed, heavy duty No. 14/3 AWG industrial grade 3-

wire type. Use of larger numerical gauge (lower capacity wire) power cord(s) may result in electrical shock,
fire hazards and/or damage to unit. The cord(s) must be in good condition and in continuous lengths (no
splicing) and should not exceed a total of 50 feet in length. Make certain that any extension cords used do
not reduce power to the unit to less than 110 volts. Use of a voltmeter to confirm adequate voltage is
recommended.

4.   Check to ensure that any circuit to which the unit is connected is protected by a 15 ampere circuit breaker.

The unit itself is equipped with a 12 amp circuit breaker.

5.   The PRED1200 should be connected to a three-prong, properly grounded electrical outlet equipped with a

Ground Fault Circuit Interrupt (GFCI) device. A GFCI is an electrical safety device that will trip the circuit and
stop the flow of electricity if leakage of current is detected.

Important Note: The GFCI on the PRED1200 control panel only detects leakage of current from the
unit or an electrical device plugged into the GFCI. The PRED1200 should be plugged into a GFCI
receptacle at the power source to protect the power cord and the unit. This GFCI will trip the
circuit if it detects leakage of current from the power cord or unit.

6.   To avoid personal injury, fire hazards and/or damage to the PRED1200 electrical system and power cord,

do not connect or disconnect the power cord to an electrical outlet unless the motorized impeller is “OFF”.

Summary of Contents for PRED1200

Page 1: ...1200 ModelPRED1200 ModelPRED1200 ModelPRED1200 ModelPRED1200 INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL INSTRUCTION MANUAL Abatement Technologies Ltd Ontario Canada 905 871 4720 Abatement Technologies Inc Georgia USA 800 634 9091 PRED1200MNL rev 6 30 2009 Abatement Technologies Inc Remediation Products Division www abatement com Patented U S Design Patent No D572 3...

Page 2: ...Pre filter P N H502 3 OptionalThird Stage 2 High Capacity Vapor Lock Carbon Filter P N VL1002 4 Final Stage 99 97 HEPA Filter P N H610C 99 5 Motorized Impeller 6 8 Rear Wheels 7 360 Swivel Casters 8 Pre filter Access Door 9 HEPA Filter Access Panel 10 Control Panel 11 Exhaust Outlet ...

Page 3: ...y known as OVG is also available Types of contaminants captured by particulate pre filters HEPA filter or carbon filters Dirt Dust Drywall dust Saw dust Note To capture low concentrations of OVG a Vapor Lock carbon filter must be used The PRED1200 is capable of providing particulate and odor vapor gas filtration with final stage filtration through a High Efficiency Particulate Air HEPA filter The ...

Page 4: ...re accurate rule of thumb than one s sense of smell Since off gassing of adsorbed OVG can occur when the adsorption capacity of the filter is reached replace the carbon filter as soon as odor breakthrough is sensed More detailed information on carbon adsorption can be found in an article titled Activated Carbon How Is It Used How Does It Work which can be found on the Links and Articles page of th...

Page 5: ...ary start up current surge the unit requires a 15 amp circuit that is free of other loads 3 Extension cords used for the PRED1200 must be UL listed heavy duty No 14 3 AWG industrial grade 3 wire type Use of larger numerical gauge lower capacity wire power cord s may result in electrical shock fire hazards and or damage to unit The cord s must be in good condition and in continuous lengths no splic...

Page 6: ...of electrical shock Can cause injury or death Turn unit OFF and disconnect power cord from supply receptacle before replacing the HEPA filter and before cleaning or servicing the unit Warning The PRED1200 is equipped with an automatic restart motorized impeller that will restart without warning after a temporary power interruption or recovery from a thermal overload over heating condition Keep cle...

Page 7: ...ing the total amperage draw BEFORE OPERATING THE UNIT NOTE THE FOLLOWING Inspect and tighten any HEPA filter retaining nuts that may have loosened during transportation Inspect the filters for any material or structural damage prior to use and replace any damaged filters before operating the unit When removing any filters prior to operation always put them back in place with airflow indicator on f...

Page 8: ...nel are in place and closed DAISY CHAINING Daisy Chaining refers to the operation of multiple units on one circuit with only one of the units plugged into a 120V 15A electrical power supply receptacle Each subsequent unit is plugged into one of the GFCI receptacles on the prior unit up to the maximum number allowed based on the amperage draw per unit The National Electrical Code limits the total a...

Page 9: ...usable therefore do not attempt to clean and reuse them Caution Abatement Technologies PRED1200 Portable Air Scrubber units are designed to meet or exceed standards for high efficiency air filtration equipment Use only Abatement Technologies parts including replacement filters Use of non Abatement Technologies parts and filters voids the product warranty and all performance claims Warning To reduc...

Page 10: ...e HEPA filter retaining bracket in place slide the bracket off the long filter retaining bolts and remove the HEPA filter 4 Carefully place a new HEPA filter part H610C 99 into the cabinet making sure that it rests on the curved section of the cabinet base which is just behind the long lower filter retaining bolt The foam seal of the filter should be aligned with the exhaust outlet 5 Place the HEP...

Page 11: ...r o o d d e g n i h g n i t a r e p o y s a E s s a p y b r e t l i f t s n i a g a t c e t o r p o t r e t l i f e r p e g a t s t s r i F 1 2 6 F r e t l i f e r p e t a l u c i t r a p e s r a o c 1 r e t l i f e r p e g a t s d n o c e S 2 0 5 H r e t l i f e r p e t a l u c i t r a p d e t a e l p 2 e r p e g a t s d r i h t l a n o i t p O r e t l i f 2 0 0 1 L V r e t l i f n o b r a c y t ...

Page 12: ...E V O M E R H T I W E C N A D R O C C A N I E G N A H C S N O I T C U R T S N I G N I T A R E P O T C U D X E L F F O H T G N E L S D N E B E C U D E R S N O I T C I R T S E R E T A N I M I L E R O M O R F R E T L I F N O B R A C E V O M E R G A B Y L O P Note If the unit does not start or malfunctions after carefully following the Troubleshooting Guide callAbatement Technologies service departmen...

Page 13: ...om defect and to conform to specifications shall be held for Purchaser s shipping instructions which instructions Purchaser shall furnish promptly upon request ATI s liability shall in no event extend beyond replacement repair or refund of the purchase price and ATI shall not be liable under any circumstances for special contingent or consequential damages nor for loss damages or expenses directly...

Page 14: ...13 ...

Page 15: ...14 ...

Page 16: ...15 ...

Reviews: