INSTALLATION, LOCATING
The appliance should be installed in compliance with the local regulations in force
(G 638
IIworksheet, 904 worksheet: acceptance of heating installations, EN 13410, TRGI ...).
Minimum clearances to combustibles for fire prevention:
:
depending on output
-
0.5 m above the reflector
-
0.8 m sideways
-
1.5 m downward
-
1 m lenghtwise
Minimum angle of elevation of burner tube and radiant tubes
Maximum tilt angle of heater
3.1
SUSPENSION
After defining the
location of hangers,
the appliance should
be suspended using
hangers (e.g. chains) with a minimum length of 400 mm. This is required because of
longitudinal deformation due to thermal expansion. Secure the hangers from the ceiling or
8