24V dc FLEX I/O 16 Sink Input Module
9
Publication 1794ĆIN072C-EN-P - October 2001
Setting the Input Filter Time
You can select the input filter time (FT) for each group of channels (channels 00
through 11, or channels 12 through 15). Select the input filter time by setting the
corresponding bits in the output image table (complementary word) for
the module.
For example, to set a filter time of 4ms for a dc input module at address
rack 1, module group 0, set bits 05, 04, 03, 02, 01, and 00 as shown
below.
1 0 0
FT = 00-11
Fill File
Source
Destination
Length
36
#O:010
1
FLL
Write FT to complement
of input module.
O:010
00
I:000
Write Filter Time on system startup.
= 44 Octal or 36 Decimal
09 08 07 06 05 04 03 02 01 00
15 14 13 12 11 10
Dec.
1 0 0
FT = 12Ć15
Input Filter Times
Bits
Description
Selected
02
01
00 Filter Time for Inputs 00-11 (00-13)
Selected
Filter Time
05
04
03 Filter Time for Inputs 12-15 (14-17)
Filter Time
0
0
0
Filter Time 0 (default)
256
µ
s
0
0
1
Filter Time 1
512
µ
s
0
1
0
Filter Time 2
1ms
0
1
1
Filter Time 3
2ms
1
0
0
Filter Time 4
4ms
1
0
1
Filter Time 5
8ms
1
1
0
Filter Time 6
16ms
1
1
1
Filter Time 7
32ms