(Cat. No. 1794-IB16)

  

This module mounts on a 1794 terminal base unit.

1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 2

as required for this type of module.

2. Make certain the flexbus connector (3) is pushed all the way to the left

to connect with the neighboring terminal base/adapter. You cannot
install the module unless the connector is fully extended.

3. Make sure that the pins on the bottom of the module are straight so

they will align properly with the connector in the terminal base unit.

WARNING

!

If you remove or insert the module while the
backplane power is on, an electrical arc can occur.
This could cause an explosion in hazardous location
installations. Be sure that  power is removed or the
area is nonhazardous before proceeding.

4. Position the module (4) with its alignment bar (5) aligned with the

groove (6) on the terminal base.

5. Press firmly and evenly to seat the module in the terminal base unit.

The module is seated when the latching mechanism (7) is locked into
the module.

Installation Instructions

Summary of Contents for 1794-IB16

Page 1: ...the module are straight so they will align properly with the connector in the terminal base unit WARNING If you remove or insert the module while the backplane power is on an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding 4 Position the module 4 with its alignment bar 5 aligned w...

Page 2: ...perty liability for actual use based upon the examples shown in this publication Allen Bradley publication SGI 1 1 Safety Guidelines for Application Installation and Maintenance of Solid State Control available from your local Allen Bradley office describes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying p...

Page 3: ...ent is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additio...

Page 4: ...not in use keep modules in appropriate static safe packaging ATTENTION Remove field side power before removing or inserting this module This module is designed so you can remove and insert it under backplane power When you remove or insert a module with field side power applied an electrical arc may occur An electrical arc can cause personal injury or property damage by sending an erroneous signal...

Page 5: ...C for each input as indicated in the table below The V dc power terminals of row C are internally connected together 3 Connect the associated input common 3 wire devices only to the corresponding terminal on the 16 33 row B for each input as indicated in the table below Commons are internally connected together 4 Connect V dc power to terminal 34 on the 34 51 row C 5 Connect dc return to terminal ...

Page 6: ...12 13 14 15 18 19 20 21 22 23 33 24 25 26 27 28 29 30 31 32 17 35 36 37 38 47 48 49 50 34 51 16 39 40 41 42 43 44 45 46 ATTENTION Total current draw through the terminal base unit is limited to 10A Separate power connections to the terminal base unit may be necessary ...

Page 7: ...3 Input 7 A 7 C 42 B 24 Input 8 A 8 C 43 B 25 Input 9 A 9 C 44 B 26 Input 10 A 10 C 45 B 27 Input 11 A 11 C 46 B 28 Input 12 A 12 C 47 B 29 Input 13 A 13 C 48 B 30 Input 14 A 14 C 49 B 31 Input 15 A 15 C 50 B 32 V dc C 34 thru C 51 1794ĆTB3 ĆTB3S Common B 16 thru B 33 1 3Ćwire devices only 24V dc Common Sink Input 0 15 34 51 16 33 A B C 2Ćwire and 3Ćwire Inputs to the 1794ĆIB16 FLEX I O Module ĆTB...

Page 8: ...6 05 04 03 02 01 00 Octal 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 Read 0 D 15 D 14 D 13 D 12 D 11 D 10 D 9 D 8 D 7 D 6 D 5 D 4 D 3 D 2 D 1 D 0 Read 1 C 16 bit Counter Value of Input 15 Write Not used CF CR Not used FT 12 15 FT 00 11 Where D Data Input 0 input off 1 input on C Counter value for input 15 FT Input Filter Time CR Counter Reset CF Counter Fast where 1 Fast Input raw data 0 Stan...

Page 9: ... 05 04 03 02 01 and 00 as shown below 1 0 0 FT 00 11 Fill File Source Destination Length 36 O 010 1 FLL Write FT to complement of input module O 010 00 I 000 Write Filter Time on system startup 44 Octal or 36 Decimal 09 08 07 06 05 04 03 02 01 00 15 14 13 12 11 10 Dec 1 0 0 FT 12Ć15 Input Filter Times Bits Description Selected 02 01 00 Filter Time for Inputs 00 11 00 13 Selected Filter Time 05 04 ...

Page 10: ...ains batteries they must only be changed in an area known to be nonhazardous Informations sur l utilisation de cet équipement en environnements dangereux Les produits marqués CL I DIV 2 GP A B C D ne conviennent que une utilisation en environnements de Classe I Division 2 Groupes A B C D dangereux et non dangereux Chaque produit est livré avec des marquages sur sa plaque d identification qui indiq...

Page 11: ...s Input FilterTime Off to On On to Off 256µs 512µs 1ms 2ms 4ms 8ms 16ms 32ms 256µs 512µs 1ms 2ms 4ms 8ms 16ms 32ms 256µs default Selectable thru output image table Flexbus Current maximum 30mA Power Dissipation Maximum 6 1W 31 2V dc Thermal Dissipation Maximum 20 8 BTU hr 31 2V dc Indicators field side indication customer device driven 16 yellow status indicators Keyswitch Position 2 External dc P...

Page 12: ... IEC 60068 2 6 Test Fc Operating 5g 10 500Hz ESD Immunity IEC 61000 4 2 4kV contact discharges 8kV air discharges Radiated RF Immunity IEC 61000 4 3 10V m with 1kHz sine wave 80 AM from 30MHz to 1000MHz EFT B Immunity IEC 61000 4 4 2kV 5kHz on signal ports Surge Transient Immunity IEC 61000 4 5 1kV line line DM and 2kV line earth CM on signal ports Conducted RF Immunity IEC 61000 4 6 10V rms with ...

Page 13: ...h AS NZS 2064 Industrial Emissions 1 You use this conductor category information for planning conductor routing as described in the system level installation manual 2 See the Product Certification link at www ab com for Declarations of Conformity Certificates and other certification details This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directi...

Page 14: ...g ALCR is to be considered as applicable to individual products Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I Zone 2 environments This equipment must be powered by energy limited associated equipment as defined in EN 50021 when applied in Class I Zone 2 environments Provision shall be made to prevent the rated...

Page 15: ... The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V dc supply voltages and ambient temperatures Normal mounting safe operating range includes Other mounting positions including inverted horizontal safe operating range 37 32 28 5 27 5 Normal Mounting Horizontal Other Mounting including Vertical and Inverted Horizontal Mounting ...

Page 16: ...ajor offices worldwide World Headquarters AllenĆBradley 1201 South Second Street Milwaukee WI 53204 USA Tel 1 414 382Ć2000 Fax 1 414 382Ć4444 Pub 1794ĆIN072C EN P October 2001 Supersedes publication 1794Ć5 4 September 1999 PN957626 48 Copyright 2001 AllenĆBradley Company Inc Printed in USA ...

Reviews: