LCD SCREENS
Setpoint Status Screens
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint
Status Screens. From the SETPOINT STATUS Screen, press
<ENTER>
to scroll through the screens.
SETPOINT
STATUS
COILT SP
35 DEG
COIL TEMPERATURE SETPOINT STATUS
Valid range is 35 to 70 degrees. Default is 35 degrees.
IF CONFIGURED FOR MODULATING CONDENSER,
THE FOLLOWING SCREEN WILL DISPLAY
HEADPRSP
340 PSI
HEAD PRESSURE SETPOINT STATUS
Valid range is 275 to 475 PSI. Default is 340 PSI.
IF CONFIGURED FOR FAN CYCLE, THE
FOLLOWING TWO SCREENS WILL DISPLAY
FAN ON
XX PSI
HEAD PRESSURE HEADING WHEN FAN CYCLE IS ON
FAN OFF
XX PSI
HEAD PRESSURE READING WHEN FAN CYCLE IS OFF
IF CONFIGURED WATER SOURCE HEAT PUMP,
THE FOLLOWING THREE SCREENS WILL DISPLAY
GLYCOL %
%
GLYCOL PERCENTAGE STATUS
LOW SUCT
95 PSI
LOW SUCTION PRESSURE SETPOINT STATUS
Default is 95 PSI.
LOW H2O
37 DEGF
LOW LEAVING WATER TEMPERATURE SETPOINT STATUS
Default is 37ºF.
IF CONFIGURED FOR AIR TO AIR HEAT PUMP,
THE FOLLOWING SCREEN WILL DISPLAY
DEFR INT
30 MIN
DEFROST INTERVAL SETPOINT STATUS
Default is 30 minutes.