Table 4 - Ramp Up Procedure
Stage
Description
Target Frequency
(Hz)
Ramp Up Rate
(Hz/s)
Duration
(S)
I
Compressor command started.
20
10
2
II
Compressor reaches minimum start frequency.
25
1
5
III
Compressor remains at platform frequency.
25
-
10
IV
Compressor reaches commanded frequency.
Commanded
1
-
Table 5 - Ramp Down Sequence
Stage
Description
Target Frequency
(Hz)
Ramp Down Rate
(Hz/s)
I
Compressor gets to 30Hz
30
2
II
Compressor gets to minimum frequency
15
2.5
III
Compressor stop
-
-