8
1.
Startup and service must be performed by
a Factory Trained Service Technician
2.
The unit is for outdoor use only. See
General Information section for more
information.
3.
Every unit has a unique equipment
nameplate with electrical, operational,
and unit clearance specifications. Always
refer to the unit nameplate for specific
ratings unique to the model you have
purchased.
4.
READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL.
OTHER
IMPORTANT
SAFETY
PRECAUTIONS
ARE
PROVIDED THROUGHOUT THIS
MANUAL.
5.
Keep this manual and all literature
safeguarded near or on the unit.
Some
chemical
coil
cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with
the
manufacturer
’s
usage
instructions.
Failure
to
follow
instructions may result in equipment
damage, injury or death.
WARNING
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils will
cause high pressure inside the coil
tubing and damage to the coil.
CAUTION
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 3 minutes.
3 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 3 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING