45
The following settings are available for “Event Register Menu”
(see Figure 5.7):
a) Event Register Status (Read Only)
Each active Alarm Event will be indicated on the LCD screen. In addidtion
the total number of currently active events will be displayed on the first
line (header). A typical display without active diagnostic and Alarm Events
is shown below.
A typical display with two active events is shown below.
If more than 7 events are displayed, the user can use
UP
and
DN
buttons
to scroll and see all indicated events. If the event is not latched in the
Event Latch Mask Register it may appear and disappear from the status
screen and will be indicated as long as actual event is taking place.
b) Event Latch Mask (Tabular entry)
Using Event Latch Mask settings the user can enable (unmask) or disable
(mask) the latch feature individually for each event. The event is enabled
if an asterisk sign [*] is set to the right across from the corresponding
event. If the event is not latched (no aste.risk across from the
corresponding event) it may appear and disappear from the status screen.
It will be indicated as long as the actual event is taking place. By default
the unit is shipped from the factory with only one event active: 0 – CPU
Temperature Too High. For all other events the latch feature is disabled.
A typical display with Event Latch Mask selection is shown below.
Event Reg. Status: 0
No Active Events
Event Reg. Status: 2
2 - Low Flow Alarm
B - Power On Event
Summary of Contents for TIO
Page 14: ...10 Figure 4 3 RS 485 Multidrop Half Duplex Two Wire System...
Page 55: ...51 Figure 6 2 Connecting TIO to the GFM using 0 5 Vdc output from DB9 connector...
Page 56: ...52 Figure 6 3 Connecting TIO to the GFM using 5 10 Vdc output from RJ11 connector...
Page 57: ...53 Figure 6 4 Connecting TIO to the GFM using 4 20 mA output from DB9 connector...
Page 61: ...58 Figure 6 6 Connecting TIO to the GFC Using 0 5Vdc Input Output from DB15 Connector...
Page 62: ...59 Figure 6 7 Connecting TIO to the GFC Using 4 20mA Input Output from DB15 Connector...
Page 68: ...65 Figure 6 9 Connecting TIO to the Generic Flow Meter...
Page 69: ...66 Figure 6 10 Connecting TIO to the Generic Flow Controller...
Page 95: ...92 APPENDIX D Mechanical Drawings...
Page 96: ...93 APPENDIX E Circuit Layout Diagrams Circuit Layout Top...