13
5.
LCD KEY-PAD OPERATION: DATA ENTRY AND
CONFIGURATION
5.1 Display
Indications
Initially, after the power is first turned on, the Banner Screen is shown for 2 sec-
onds, then device firmware and EEPROM data base table revisions on the first line,
communication interface type on the second line, baud rate and RS-485 hexadec-
imal address value on third and fourth lines are shown for another 2 seconds.
Subsequently, the actual process information (PI) is displayed.
Figure 5.1: TIO Firmware and Communication Interface Info Screen
Based on device configuration (Device Function as flow meter or flow controller),
different parameters may be displayed in the Process Information (PI) screen by
pressing the
UP
or
DN
pushbuttons.
Process Information screens can be configured to be static or dynamic (see
Paragraph 5.3.11 “Display Menu”). Using Screen Mask settings user can enable
(unmask) or disable (mask) up to 4 different process information combinations
(see Figure 5.4). In the Static Mode the
UP
button pages through the PI screens
in the forward direction, the
DN
button pages through the PI screens in the reverse
direction. When the last PI screen is reached, the firmware “wraps around” and
scrolls to the initial PI screen once again.
In the Dynamic Display Mode, firmware initiates automatic screen sequencing with
user- adjustable screen Cycle Time (see Paragraph 5.3.11 “Display Menu”). When
the last PI screen is reached, the firmware “wraps around” and scrolls to the ini-
tial PI screen once again.
Fw: A002 Tbl: A001
Interface: RS-232
Baud Rate: 9600
RS485 address: 11
NOTE: Actual content of the LCD screen may vary depending on the
model and device configuration.
,
Summary of Contents for TIO
Page 14: ...10 Figure 4 3 RS 485 Multidrop Half Duplex Two Wire System...
Page 55: ...51 Figure 6 2 Connecting TIO to the GFM using 0 5 Vdc output from DB9 connector...
Page 56: ...52 Figure 6 3 Connecting TIO to the GFM using 5 10 Vdc output from RJ11 connector...
Page 57: ...53 Figure 6 4 Connecting TIO to the GFM using 4 20 mA output from DB9 connector...
Page 61: ...58 Figure 6 6 Connecting TIO to the GFC Using 0 5Vdc Input Output from DB15 Connector...
Page 62: ...59 Figure 6 7 Connecting TIO to the GFC Using 4 20mA Input Output from DB15 Connector...
Page 68: ...65 Figure 6 9 Connecting TIO to the Generic Flow Meter...
Page 69: ...66 Figure 6 10 Connecting TIO to the Generic Flow Controller...
Page 95: ...92 APPENDIX D Mechanical Drawings...
Page 96: ...93 APPENDIX E Circuit Layout Diagrams Circuit Layout Top...