33
PulsePak Prime
GDED-IOM-216-B
7.
Inspect new cartridges for damage from shipping, storage or handling.
DO NOT use damaged cartridges.
8.
Slide the new cartridges onto the support mandrels gasket end first.
While installing cartridges, be careful that cartridges do not contact the
housing etc. which might damage or puncture the cartridges.
9.
Tighten each cartridge to ensure that the gasket is sealed against the
back wall.
10.
Swing closed each cartridge access door. Ensure the cam action door
closure mechanism engages with the stop. Fully lower the clamping handle
which pulls the door closed and seals the cartridge by slightly compressing the
gaskets.
11.
Re-open the compressed air isolation valve.
12.6
Accessories
AAF accessories should be inspected for wear or damage on the same interval
as the cartridges.
Any accessory equipment should follow the maintenance schedule that is
included in the manufacturer’s IOM.
See final page of IOM for Maintenance Interval Checklist.