background image

7

To reduce the risk of excessive pressures and temperatures 
in this water heater, install temperature and pressure relief 
protective equipment required by local codes, but no less 
than a combination temperature and pressure relief valve 
certi

fi

 ed by a nationally recognized testing laboratory that 

maintains periodic inspection of the production of listed 
equipment or materials, as meeting the requirements for 
Relief Valves and Automatic Shutoff Devices for Hot Water 
Supply Systems, ANSI Z21.22 - latest edition. This valve 
must be marked with the maximum set pressure not to 
exceed the marked maximum working pressure of the 
water heater. Install the valve into an opening provided 
and marked for this purpose in the water heater, and orient 
it or provide tubing so that any discharge from the valve 
exits only within 6 inches above drain, or at any distance 
below, the structural 

fl

 oor, and does not contact any live 

electrical part. The discharge opening must not be blocked 
or reduced in size under any circumstance. 

IMPORTANT:

  Only a new temperature and pressure relief 

valve should be used with your water heater. Do not use an 

old or existing valve as it may be damaged or not adequate 

for the working pressure of the new water heater. Do not 

place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:   

• 

Shall not be in contact with any electrical part.

• 

Shall be connected to an adequate discharge line.

• 

Shall not be rated higher than  the working pressure  
shown on the data plate of the water heater.

The Discharge Line:

• 

Shall not be smaller than the pipe size of the relief  
valve or have any reducing coupling installed in the 
discharge line.

• 

Shall not be capped, blocked, plugged or contain    
any valve between the relief valve and the end of the 
discharge line.

• 

Shall terminate a maximum of six inches above a floor 
drain or external to the building. In cold climates, it is 
recommended that the discharge pipe be terminated at 
an adequate drain inside the building.

• 

Shall be of material listed for hot water distribution.

• 

Shall be installed to allow complete drainage of both 
the valve and discharge line.

Temperature/Pressure Relief Valve and 
Pipe Insulation

Locate the temperature and pressure relief valve on the 

1. 

water heater (also known as a T&P relief valve). See 

Figure 5.
Locate the slit running the length of the T&P relief valve 

2. 

insulation.
Spread the slit open and 

fi

 t the insulation over the T&P 

3. 

relief valve. See Figure 6. Apply gentle pressure to the 

insulation to ensure that it is fully seated on the T&P Re-

lief Valve. Once seated, secure the insulation with duct 

tape, electrical tape, or equivalent. 

IMPORTANT:

 The insulation and tape must not block 

the discharge opening or hinder access to the manual 

relief lever (Figure 6). Ensure a discharge pipe is in-

stalled into the T&P valve discharge opening per the 

instructions in this manual.

Temperature and Pressure 
Relief Valve

Explosion Hazard

If the temperature and pressure relief valve 
is dripping or leaking, have a qualified 
person replace it.

Examples of a qualified person include:
licensed plumbers, authorized electric 
company personnel, and authorized service 
personnel.

Do not plug valve.

Do not remove valve.

Failure to follow these instructions can 
result in death or explosion.

WARNING

6” Maximum 
Air Gap

Drain Pan 2 1/2” 
Depth Maximum and
2 Inches wider than
the water heater.

Discharge Pipe
(Do Not Plug or Cap)

Temperature and 
Pressure Relief Valve

Drain Line 3/4” 
ID Minimum

Drain

Figure 5
Temperature and Pressure 
Relief Valve Installation 

For protection against excessive pressures and 
temperatures, a temperature and pressure relief valve must 
be installed in the opening marked “T & P RELIEF VALVE” 
(See Figure 5).

Summary of Contents for Voltex Hybrid Electric PHPT-80

Page 1: ...Information 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Che...

Page 2: ...extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appli...

Page 3: ...ipt as proof of purchase Basic Operation Fundamentals The Heat Pump Water Heater HPWH is an integrated heat pump water heater unit having an 850 watt compressor and external coil heat exchanger with b...

Page 4: ...ead all instructions before attempting to assemble and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the...

Page 5: ...own in Figure 4 If installing the water heater in a closed water system 5 install an expansion tank in the cold water line as specified under Closed System Thermal Expansion Install a shut off valve i...

Page 6: ...es Use appropriate primer and glue to cement the condensate drain lines to the heat pump drain pan NOTE The heat pump drain pan is ABS and the two condensate drain pipes should be PVC If a condensate...

Page 7: ...ve and the end of the discharge line Shall terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at...

Page 8: ...led with water and all air is purged from the tank before making any electrical connections See Draining and Flushing Section Turn off power to the electrical wiring for the water heater at 2 the circ...

Page 9: ...Press the power button to turn the water heater on 8 and select the desired operational mode After about 8 minutes the heat pump will turn on Test the operation of the shut off switch by unplugging 9...

Page 10: ...free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section Mixing valve when app...

Page 11: ...ing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature Regulation Water temperature over 125 F...

Page 12: ...the User Interface are touch sensitive and require only a light touch to actuate EFFICIENCY Efficiency Mode Is the most energy efficient mode This mode uses the heat pump to heat water in the tank The...

Page 13: ...rd These noises are common and may result from the following Normal expansion and contraction of metal parts 1 during periods of heat up and cool down Sediment buildup on or around the elements could...

Page 14: ...ORTANT Do not turn on power to the water heater unless it is completely filled with water To ensure that the tank is full open a hot water faucet and allow the water to run until the air is purged and...

Page 15: ...ir Filter Remove and inspect clean if needed and reinstall Condensate drain pan and condensate lines The lower metal drain pan for standing water which may indicate a clogged condensate drain pan cond...

Page 16: ...OPEN OR AD ERROR 1 Upper Temperature Sensor is not functioning Contact a qualified person to service the unit 1 LOWER TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Lower Temperature Sensor is not functionin...

Page 17: ...is at the top Insulate exposed piping 5 Repair hot water leaks 6 Call qualified person for service 7 Drain and flush tank Water conditioning may 8 be necessary to minimize build up HIGH OPERATION COS...

Page 18: ...4 Drain Valve 15 Protective Plastic Cover 16 ECO Cover 17 Control Board 18 Relay 19 EPS Cover 20 Ambient Coil Discharge Temperature Sensor 21 Upper Lower Tank Temperature Sensor 22 Run Capacitor 23 Co...

Page 19: ...19 NOTES...

Page 20: ...20 Copyright 2010 A O Smith Corporation All rights reserved...

Reviews: