background image

10

Water Heater Location

Centrally located with the water piping system.

 

The 

fl

 ooring beneath the water heater must be able to 

 

support the weight of the water heater when 

fi

 lled with 

water (967 lbs. full).

Located indoors (such as a basement or garage) 

 

and in a vertical position. Sheltered from freezing 
temperatures.
Provisions made to shelter the area from water    

 

damage. Metal drain pan installed and piped to an 
adequate drain.
Sufficient room to service the water heater.

 

Sufficient air for the heat pump to function. 

 

The water 

heater must be located in a space 750 cubic feet or 
larger, and must have unrestricted air

fl

 ow.  As an 

example, a room that has an 8 foot tall ceiling and is 
10 feet long by 9-1/2 feet wide would contain 760 cubic 
feet. 

 

NOTE:

 For optimal ef

fi

 ciency and serviceability, the 

following clearances should be maintained: 3 feet on 
the air inlet side, 5 feet on the air outlet side, 6 inches in 
the back, and 2 feet in the front.

 

The unit cannot be placed into any type of closet or 

 

small enclosure.
The site location must be free from any corrosive 

 

elements in the atmosphere such as sulfur, 

fl

 uorine, 

and chlorine. These elements are found in aerosol 
sprays, detergents, bleaches, cleaning solvents, air 
fresheners, paint, and varnish removers, refrigerants, 
and many other commercial and household products. 
In addition excessive dust and lint may affect the 
operation of the unit and require more frequent 
cleaning (See “Cleaning the Heat Pump” section).
Ambient air temperature must be above 45°F and 

 

below 109°F. If the ambient air temperature falls 
outside these upper and lower limits the electrical 
elements will activate to meet the hot water demand.

Water System Piping

Temperature and pressure relief valve properly    

 

installed with a discharge pipe run to an adequate drain  
and sheltered from freezing (See Figure 5).
All piping properly installed and free of leaks.

 

Heater completely filled with water (See “Water Piping 

 

System” section).
Closed system pressure buildup precautions installed 

 

(See “Closed System/Thermal Expansion” section).
Mixing valve (when applicable) installed per 

 

manufacturer’s instructions (See “Water Temperature 
Regulation” section).

INSTALLATION CHECKLIST

Condensate Drain Line Installation

Must be located with access to an adequate drain or 

 

condensate pump.
Condensate drain lines installed and piped to an 

 

adequate drain or condensate pump (See Figure 4).

Electrical Connections

The water heater requires 240 VAC for proper 

 

operation.
Wiring size and connections comply with all applicable  

 

codes or in the absence of local or state codes follow 
NFPA-70, the National Electrical Code-current edition.
Water heater and electrical supply are properly    

 

grounded.
Wiring enclosed in approved conduit (if required by 

 

local codes).

Proper overload fuse or circuit breaker protection 

 

installed.

Post Installation Review

Understand how to use the User Interface Module to 

 

set the various modes and functions (See “Adjusting 
the User Interface Module/Operating Modes” section). 
Hybrid Mode is the recommended Operating Mode. 

 

Understand the various Operating Modes and which 
mode may be best based on season, ambient 
temperature, and usage (See “Operating Mode 
Description” section). 

NOTE:

 It may be necessary to temporarily change 

modes if for example filling a spa or hot tub.
Understand the importance of routine inspection/

 

maintenance of the condensate drain pan and lines 
(See “

Inspection/Cleaning of the Condensate Drain 

Pan & Condensate Drain Lines” section)

.  This is to 

help prevent any possible drain line blockage resulting 
in the condensate drain pan overflowing. 

IMPORTANT:

 Water coming from the plastic shroud is 

an indicator that both condensation drain lines may be 
blocked. Immediate action is required.
To maintain optimal operation check, remove and clean 

 

the air filter (See “Air Filter Cleaning/Replacement” 
section).
The Installation Instructions and Use & Care Guide 

 

should be kept with the water heater for reference. 

Summary of Contents for Voltex Hybrid Electric PHPT-80

Page 1: ...Information 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Che...

Page 2: ...extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appli...

Page 3: ...ipt as proof of purchase Basic Operation Fundamentals The Heat Pump Water Heater HPWH is an integrated heat pump water heater unit having an 850 watt compressor and external coil heat exchanger with b...

Page 4: ...ead all instructions before attempting to assemble and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the...

Page 5: ...own in Figure 4 If installing the water heater in a closed water system 5 install an expansion tank in the cold water line as specified under Closed System Thermal Expansion Install a shut off valve i...

Page 6: ...es Use appropriate primer and glue to cement the condensate drain lines to the heat pump drain pan NOTE The heat pump drain pan is ABS and the two condensate drain pipes should be PVC If a condensate...

Page 7: ...ve and the end of the discharge line Shall terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at...

Page 8: ...led with water and all air is purged from the tank before making any electrical connections See Draining and Flushing Section Turn off power to the electrical wiring for the water heater at 2 the circ...

Page 9: ...Press the power button to turn the water heater on 8 and select the desired operational mode After about 8 minutes the heat pump will turn on Test the operation of the shut off switch by unplugging 9...

Page 10: ...free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section Mixing valve when app...

Page 11: ...ing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature Regulation Water temperature over 125 F...

Page 12: ...the User Interface are touch sensitive and require only a light touch to actuate EFFICIENCY Efficiency Mode Is the most energy efficient mode This mode uses the heat pump to heat water in the tank The...

Page 13: ...rd These noises are common and may result from the following Normal expansion and contraction of metal parts 1 during periods of heat up and cool down Sediment buildup on or around the elements could...

Page 14: ...ORTANT Do not turn on power to the water heater unless it is completely filled with water To ensure that the tank is full open a hot water faucet and allow the water to run until the air is purged and...

Page 15: ...ir Filter Remove and inspect clean if needed and reinstall Condensate drain pan and condensate lines The lower metal drain pan for standing water which may indicate a clogged condensate drain pan cond...

Page 16: ...OPEN OR AD ERROR 1 Upper Temperature Sensor is not functioning Contact a qualified person to service the unit 1 LOWER TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Lower Temperature Sensor is not functionin...

Page 17: ...is at the top Insulate exposed piping 5 Repair hot water leaks 6 Call qualified person for service 7 Drain and flush tank Water conditioning may 8 be necessary to minimize build up HIGH OPERATION COS...

Page 18: ...4 Drain Valve 15 Protective Plastic Cover 16 ECO Cover 17 Control Board 18 Relay 19 EPS Cover 20 Ambient Coil Discharge Temperature Sensor 21 Upper Lower Tank Temperature Sensor 22 Run Capacitor 23 Co...

Page 19: ...19 NOTES...

Page 20: ...20 Copyright 2010 A O Smith Corporation All rights reserved...

Reviews: