background image

18

Any safety devices including low water cutoffs used in conjunction 

with this boiler should receive periodic (every six months) inspection 

to assure proper operation. A low water cutoff device of the float 

type should be flushed every six months. Periodic checks, at least 

twice a year, should be made for water leaks.
More frequent inspections may be necessary depending on water 

conditions.
The boiler-mounted gas and electrical controls have been designed 

to give both dependable service and long life. However, malfunction 

can occur, as with any piece of equipment. It is therefore 

recommended that all components be checked periodically by a 

qualified service agent for proper operation.

RELIEF VALVE

Burn hazard.

Hot water discharge.

Keep clear of Pressure

Relief Valve discharge outlet.

The pressure relief valve must be manually operated at least 

once a year. Caution should be taken to ensure that (1) no one 

is in front of or around the outlet of the pressure relief valve 

discharge line, and (2) the water manually discharged will not 

cause any bodily injury or property damage because the water 

may be extremely hot.
To test the relief valve, lift the lever at the end of the valve several 

times, see Figure below. The valve should seat properly and 

operate freely.

DISCHARGE

PIPE

RELIEF VALVE

FIGURE 4. - RELIEF VALVE

If after manually operating the valve, it fails to completely reset 

and continues to release water, turn off power to the boiler at the 

main disconnect switch or breaker. Close the cold water inlet to the 

boiler and follow the draining instructions in this manual to drain 

the boiler. Should the relief valve need to be replaced, call the toll 

free phone number listed on the back of this manual for further 

technical assistance.

COMBUSTION AIR FILTER

If the combustion air supply to the boiler contains dust, dirt, drywall 

dust etc. a filter must be installed. An air filter is not supplied with 

the boiler as shipped from the factory. The installer must provide a 

filtering system in the air inlet  to the boiler if dust, dirt or construction  

dirt can be pulled into the boiler through the inlet air piping. 

Periodically clean air filter per the manufacturer’s instructions.

BLOWER COMPARTMENT

The blower compartment should be cleaned annually to remove any 

dirt and lint that may have accumulated in the compartment or on the 

blower and motor. Buildups of dirt and lint on the blower and motor 

can create excessive loads on the motor resulting in higher that 

normal operating temperatures and possible shortened service life.

BURNER MAINTENANCE

Qualified servicers should follow this procedure when the boiler’s 

burner needs cleaning.
1. Turn off the electrical power to the boiler and close the main 

manual gas shutoff valve(s). Allow the boiler parts to cool before 

disassembly.

2. 

Loosen the flange and separate the gas train from the manifold 

assembly.

3. 

Separate the burner from the blower adapter by first removing 

the four (4) bolts and subsequently, the blower gas kets. The 

blower should be free to move at this point.

FoR DIRECT vENT UNITS: It is necessary to loosen and slide the 

rubber coupling on the blower adaptor in order to move the blower.
4. loosen the seven bolts on the blower adapter at the base and 

move the burner ground wire (Green) aside.

5. lift the blower adapter and remove the manifold assembly up 

from the 6 studs located on the cover plate and remove the 

burner gasket.  

6. Remove any loose foreign material such as dust or lint with a 

vacuum. Check all ports for blockage.  Dislodge any foreign 

material causing blockage. Remove any soot or carbon deposits 

with a rag making sure to remove any lint  left on the burner by 

vacuuming again.

7. Reverse the steps to reassemble the unit.

8. Restore electrical power and gas supply to the boiler.

• 

Put the boiler back in operation by following the lighting and 

operating instructions in this manual.

• 

Check for gas leaks and proper boiler and vent operation.

CONDENSATE REMOVAL SYSTEM

Due  to  the  highly  efficient  operation  of  this  unit,  condensate  is 

formed during operation and must be removed by the conden sate 

drain systems. Inspect the condensate drains and tubes at least 

once a month and insure they will allow the free flow of condensate 

at all times. The system must be inspected more frequently in 

cold weather if the drain system is located in an area, such as 

along the floor, where freezing tempera tures are likely to occur. 

The condensate drain system must be protected against freezing. 

Contact a qualified service agent to inspect and correct the condition 

if freezing of the conden sate lines is a problem. The unit is equipped 

with a blocked flue switch which will shut the unit off if condensate 

is unable to drain and backs up in the unit. A blocked flue error will 

appear when sufficient condensate accumulates for this condition.

The transparent drain lines and condensate drain on the bottom 

of the vent collector should be visually inspected at one month 

intervals for blockage, particularly in the areas of the loops in the 

lines which trap a small amount of conden sate, and the exit point 

of the vent collector drain.  Conden sate in portions of the line other 

than the loop area indicates a blockage in the drain line.  Flush the 

Summary of Contents for VF VB 500

Page 1: ...e any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installati...

Page 2: ...nces known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...trol assembly pro vided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refe...

Page 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 6: ...6 CONNECTION DIAGRAM...

Page 7: ...7...

Page 8: ...8 Figure 1 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Page 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Page 10: ...stem or something similar Through this connection multiple boilers can also be linked together CAUTION The internal communications cables should never be connected to the external communications conne...

Page 11: ...me rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio d...

Page 12: ...u activated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches al...

Page 13: ...jump to the error state Description of FCB control states Idle State When any error is declared during idle state The system will remain in this state until the MCB request a heating cycle or a cold...

Page 14: ...to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is poin...

Page 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Page 16: ...ected wiring Note The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connectorattheendoftheprobecable Thevalueshouldbea...

Page 17: ...Give reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check fo...

Page 18: ...ible shortened service life BURNER MAINTENANCE Qualified servicers should follow this procedure when the boiler s burner needs cleaning 1 Turn off the electrical power to the boiler and close the main...

Page 19: ...solidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime released f...

Page 20: ...20 notes...

Page 21: ...21 notes...

Page 22: ...22 notes...

Page 23: ...ation for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you 5 CLAIM PROCEDURE Any cla...

Page 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: