background image

12

the temperature is less than the operating setpoint minus the 

differential temperature and the thermostat input is closed then 

a call for heat is established and the system shifts to the run 

mode (green “Running” lED turns on).

5.  The heating sequence begins by applying power to the pump.
6.  After a few seconds the blower is turned on for 30-second 

pre-purge period of combustion chamber.

7.  The  igniter is turned on.
8.  After the igniter has reached a minimum of 2.8 amps, the gas 

valve is energized to allow gas flow to burner.

9.  After an additional one second, the system checks the status 

of the flame through the flame rod (sensor). If the flame is not 

verified within 4 seconds, the gas valve is immediately shut 

off followed by 15-second inter-purge period, then the system 

returns to step 7, if the “Trial for Ignition” dipswitch is set for 

three (3) tries. If the dipswitch is set for one (1) trial, the system 

will declare an error and boiler will require resetting the control. 

10.  The boiler will remain running until the set point is satisfied. 

Once satisfied, the blower will continue for 15-second post 

purge period.

11.  Once set point has have been satisfied, the boiler pump will 

continue to run for the programmed post-circulate cycle.

 

12.  The control now enters the idle state as displayed by the 

“Standby” lED. The control will continue to monitor heat 

demand and state of other system devices. Upon a drop of 

water temperature below the set parameters, the control will 

return to step 5 and repeat the entire operating cycle. Note: 

Any fault detection, during standby or running modes, will halt 

the heating sequence and shift the system to the service mode 

where the detected fault will be displayed.

NoTE: In standby and running modes the system constantly 

monitors the signals and the internal operation for faults. Any 

detected fault will halt the heating sequence and shift the system 

to the service mode, where the detected fault will be displayed.

TEMPERATURE SETPOINTS (SYSTEM CONTROL ALGORITHM)

The boiler has a hysteresis type control, which means that it will 

begin heating the water when the temperature sensed by the 

control probe (inlet or tank) falls below the operating setpoint minus 

the differential setpoint.  It will stop heating the water when the 

temperature rises to the operating setpoint. 

UIM OPERATING PROCEDURES

FIGURE 2. - UIM, USER INTERFACE MODULE

The UIM receives commands from the user and displays operational 

information to the user via an lCD (liquid crystal display) up to eleven 

LED’s, and five touch switches.  The LCD provides information to 

the user by the use of 10 menu-activated screens. Within each of 
the screens, helpful information can be displayed by pressing the 

“Help” button. The lED’s visually inform the user about the mode 

the system is in. The touch switches allow the user to control the 

operation of the system. The operation of these parts is described 

in the following section:

UIM Screens:

on all screens a double vertical bar appears on the right side of 

the display each time a key is touched to indicate that a key has 

been activated. on several screens an indicator “>” appears on 

the left side of the display to indicate the active line. The “Up/

Down” keys are used to move the indicator to the desired line and 

the “Select” key is pressed to select the line. Also, on most of the 

screens, up/down arrows appear on the right side of the screen 

to indicate that there is additional lines either above or below the 

displayed four lines.

• 

Menu Screen:

  Displayed when the user presses the “Menu” key.  This screen 

is the selection point for the other 9 screens.

• 

Temperature Screen:

  Displays the sensed temperatures of the outlet, Inlet, and 

Tank probes.  Also displayed is the calculated Delta T (outlet 

minus Inlet) for the system.  Shorted (“Short”) and disconnected 

(“----”) probes are also displayed.

• 

System Status Screen:

  This screen is used to view the status of switch inputs and output 

states.  An asterisk (*) is displayed next to the label when the 

status  is  “True”  (the  description  is  fulfilled).    For  example,  if 

water is flowing, or detected by the flow sensor, then an “*” will 

appear in front of the Flow label (i.e. *Flow).  Another example 

would be the ECo switch.  If the outlet temperature is too high 

the display will show: *ECo.

The System monitors the inputs at these times:

•  ECO, Blocked Flue, Low Gas, Hi Limit, and Hi Gas - at all times 

for a fault condition.

•  Tstat - at all times for open/closed conditions. 

•  Flo

w-for an on condition when the pump is on (no check for off 

state)

•  Blower Prover - when the Blower is on.

•  Igniter Current - for an on condition approximately 18 seconds 

after the Igniter is turned on until the igniter is turned off and an 

off condition at all other times.

•  Flame - for an on condition approximately 5 seconds after the 

gas valve is turned on until the valve is turned off and at all other 

times for an off condition.

Control Status Screen:

Displays the status that the MCB micros are in. The MCB has 

5 possible states and the FCB have 9. The normal MCB states 

sequence is to move from Idle to Pre-Circulate  when a call for 

heat is initiated. Once heat has been satisfied or the Thermostat 

is opened, the sequence moves to Post-Circulate and then back to 

Idle. If a fault occurs at any time, the process jumps out of sequence 

and goes directly to the appropriate Hard or Soft Fault state.

Description of MCB control states:

•  Idle:

  The yellow “Standby” lED is turned on and the system 

Summary of Contents for VF VB 500

Page 1: ...e any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installati...

Page 2: ...nces known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...trol assembly pro vided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refe...

Page 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 6: ...6 CONNECTION DIAGRAM...

Page 7: ...7...

Page 8: ...8 Figure 1 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Page 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Page 10: ...stem or something similar Through this connection multiple boilers can also be linked together CAUTION The internal communications cables should never be connected to the external communications conne...

Page 11: ...me rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio d...

Page 12: ...u activated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches al...

Page 13: ...jump to the error state Description of FCB control states Idle State When any error is declared during idle state The system will remain in this state until the MCB request a heating cycle or a cold...

Page 14: ...to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is poin...

Page 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Page 16: ...ected wiring Note The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connectorattheendoftheprobecable Thevalueshouldbea...

Page 17: ...Give reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check fo...

Page 18: ...ible shortened service life BURNER MAINTENANCE Qualified servicers should follow this procedure when the boiler s burner needs cleaning 1 Turn off the electrical power to the boiler and close the main...

Page 19: ...solidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime released f...

Page 20: ...20 notes...

Page 21: ...21 notes...

Page 22: ...22 notes...

Page 23: ...ation for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you 5 CLAIM PROCEDURE Any cla...

Page 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Reviews: